System Setup and Setpoints – 4
4–55
MANUAL TRANSFER SETTINGS
(MTS)
Path:
System/Setup/Setpoints/Manual Transfer Settings
The Manual Transfer Settings selection from the
Transfer Settings group (Figure 4-33) opens the
Manual Transfer Settings Dialog screen (Figure
4-54),
which
includes the following tabs:
•
Setup
•
Fast Transfer
•
Delayed In-Phase Transfer
•
Residual Voltage Transfer
•
Hot Parallel Transfer
HMI Manual Transfer Enable/Disable (MBTS Front
Panel)
To enable or disable Manual Transfer from the Front
Panel perform the following:
1.
Press the
ENTER
pushbutton.
2.
If Level Access is active, the following
is displayed:
ENTER ACCESS CODE
0
a.
Input the required Access Code, then
press
ENTER
.
b.
If the proper Access Code has been
entered, the HMI will return:
LEVEL #(1,2 or 3)
Access Granted!
INIT TRANSFER
INIT
rmte_lcal
c.
Go to Step 4.
3.
If Level Access is not active, then the
following is displayed:
INIT TRANSFER
INIT
rmte_lcal
4.
Press the Right arrow pushbutton until
the following is displayed:
MANUAL TRANSFER
auto_xfer MAN_XFER
5.
Press
ENTER,
the following will be
displayed:
MANUAL TRANSFER
disable enable
6.
Press the Left or Right arrow pushbutton
as necessary to enable or disable Manual
Transfer (upper case).
7.
Press
ENTER
. The following will be
displayed:
MANUAL TRANSFER
auto_xfer MAN_XFER
8.
The MBTS is now in the selected Manual
Transfer Mode. Press
EXIT
as necessary
to return to the Main Menu.
MANUAL TRANSFER SETTINGS SETUP TAB
Path:
System/Setup/Setpoints/Manual Transfer
Settings/Setup
Figure 4-54, illustrates the MBTS Manual Transfer
Settings found under the Setup Tab on the Manual
Transfer Settings dialog screen.
Manual Transfer Settings/Manual Transfer
Mode
Manual Transfer
The Manual Transfer Mode (Figure 4-54) can be
Disabled or Enabled. If Disable is selected and then
Save is selected, then the remaining settings in the
Manual Transfer Settings dialog screen are grayed
out. There are settings in the Common Settings that
effect the operation of the Manual Transfer.
Manual Transfer Settings/External Control
Inputs Configuration
The External Control Inputs Configuration portion of
the Manual Transfer Settings dialog screen (Figure
4-54) includes the following External Control Input
configuration selections:
•
Manual Transfer Block
•
Manual Transfer Initiate
Manual Transfer/Manual Transfer Block
The Manual Transfer Block selection opens the Manual
Transfer Block dialog screen (Figure 4-55) that allows
the user to select an input that is used to block
Manual Transfers. When an input has been selected it
will be grayed out in other dialog screens that provide
input selection since it has already been assigned.
Содержание M-4272
Страница 1: ...Instruction Book Book 1 of 2 M 4272 Motor Bus Transfer System ...
Страница 45: ...xviii M 4272 Instruction Book This Page Left Intentionally Blank ...
Страница 198: ...System Setup and Setpoints 4 4 87 Figure 4 92 TCM Trip Circuit Monitor Inputs Outputs Selection Dialog Screen ...
Страница 200: ...System Setup and Setpoints 4 4 89 Figure 4 93 ISSLogic Function Dialog Screen ...
Страница 207: ...M 4272 Instruction Book 4 96 This Page Left Intentionally Blank ...
Страница 214: ...Declaration of Conformity Appendix I I 1 IAppendix I Declaration of Conformity ...
Страница 215: ...M 4272 Instruction Book I 2 This Page Left Intentionally Blank ...