Automatic Fast Transfer/Time Window
The Time Window
(Figure 4-49)
can be set from 1 to
10 cycles. The Time Window defines the window of
opportunity for a Fast Transfer. The Time Window
starts when the transfer is initiated and ends at the
selected time limit. If a Fast Transfer has not been
completed by the end of this Time Window, then the
Fast Transfer is disabled and will no longer
attempted. An In-Phase, Residual or Fixed Time
Transfer is still possible.
Closing command Time Delay is grayed out when
Common Function Settings/Transfer Mode is set to
Sequential.
Automatic Fast Transfer/Closing Command
Time Delay
The time delay can be set from 0 to 10 cycles. This
time delay is only used for Fast Transfer method in
Simultaneous transfer mode. Since the trip and
close command are normally issued at the same
time for Fast Transfer method in Simultaneous
transfer mode, this time delay allows the flexibility
to delay the closing command to accomplilsh the
break-before-make mode of operation (open
transition).
Automatic Fast Transfer/Blocking Inputs
Selection
The Blocking Inputs Selection
button (Figure 4-49)
opens the Blocking Inputs Selection dialog screen
(Figure 4-50). Any Input or the Fuse Loss (FL)
function can be selected to block a Fast Transfer.
When other functions such as External Status Reset
are selected for these inputs it will be identified next
to that input.
Automatic Fast Transfer Tab Save/Cancel
The Save selection (Figure 4-49) saves the Automatic
Fast Transfer settings either to an open file or to the
target MBTS. Cancel, returns the user to the
previous open screen.
The conditions that are necessary to execute a
Fast Transfer are:
•
No Lockout/Blocking conditions exist.
•
The phase angle between the motor bus
and the new source is within limit setting.
•
The Delta Voltage between the motor bus
and the new source is within limit setting.
•
The Delta Frequency between the motor
bus and the new source is within limit
setting.
•
A transfer must be completed within the
Fast Transfer time window of 1 to 10
cycles.
Figure 4-50 Fast Transfer Blocking Inputs Selection Dialog Screen
Содержание M-4272
Страница 1: ...Instruction Book Book 1 of 2 M 4272 Motor Bus Transfer System ...
Страница 45: ...xviii M 4272 Instruction Book This Page Left Intentionally Blank ...
Страница 198: ...System Setup and Setpoints 4 4 87 Figure 4 92 TCM Trip Circuit Monitor Inputs Outputs Selection Dialog Screen ...
Страница 200: ...System Setup and Setpoints 4 4 89 Figure 4 93 ISSLogic Function Dialog Screen ...
Страница 207: ...M 4272 Instruction Book 4 96 This Page Left Intentionally Blank ...
Страница 214: ...Declaration of Conformity Appendix I I 1 IAppendix I Declaration of Conformity ...
Страница 215: ...M 4272 Instruction Book I 2 This Page Left Intentionally Blank ...