–10–
M-4272 Digital Motor Bus Transfer System
FUNCTIONS (Cont.)
Setpoint
Ranges
Increment
Accuracy
†
Source 1 Breaker Failure (Using breaker status)
Time Delay
0 to 30 Cycles
1 Cycle
1 Cycle
The breaker failure time delay is used to monitor breaker failure when using the breaker status inputs only.
The breaker is considered failed when the breaker status has not changed state within this programmable
time delay after a trip command is issued. A separate time delay is provided for breaker failure function
(50BF) when current is present.
Source 2 Breaker Failure (Using breaker status)
Time Delay
0 to 30 Cycles
1 Cycle
1 Cycle
The breaker failure time delay is used to monitor breaker failure when using the breaker status inputs only.
The breaker is considered failed when the breaker status has not changed state within this programmable
time delay after a trip command is issued. A separate time delay is provided for breaker failure function
(50BF) when current is present.
81 Frequency (bus voltage)
Pickup #1, #2
50.00 to 67.00 Hz
0.01 Hz
0.02 Hz (
1.0 Hz)**
40.00 to 57.00 Hz*
Time Delay #1, #2
5 to 65,500 Cycles
1 Cycle
3 Cycles or
1%
The pickup accuracy applies to 60 Hz models at a range of 57 to 63 Hz, and to 50 Hz models at a range of 47
to 53 Hz. Beyond these ranges, the accuracy is
0.1 Hz (3-phase);
0.4Hz(single phase).
The 81 #1 Function can be used to initiate Load Shedding. The 81 Function is automatically disabled when the
bus phase voltage input is less than 5 to 15 V (Positive Sequence) based on the frequency, or less than 5 V
(Single Phase).
* This range applies to 50 Hz nominal frequency model.
** Value in parenthese applies to single phase bus voltage frequency.
81R Rate of Change of Frequency (bus voltage)
Pickup #1, #2
0.10 to 20.00 Hz/Sec.
0.01 Hz/Sec.
0.05 Hz/Sec. or
5%
Time Delay #1, #2
3 to 8160 Cycles
1 Cycle
+20 Cycles
Negative Sequence
Voltage Inhibit
0 to 99%
1%
0.5%
Increasing ROCOF
Enable/Disable
The 81R #1 Function can be used to initiate Load Shedding. 81R function can only be used when the bus
voltage input is three-phase, and for load shedding.
81
81R
†
Select the greater of these accuracy values. Accuracy applies to sinusoidal voltage with constant amplitude and
frequency.
Содержание M-4272
Страница 1: ...Instruction Book Book 1 of 2 M 4272 Motor Bus Transfer System ...
Страница 45: ...xviii M 4272 Instruction Book This Page Left Intentionally Blank ...
Страница 198: ...System Setup and Setpoints 4 4 87 Figure 4 92 TCM Trip Circuit Monitor Inputs Outputs Selection Dialog Screen ...
Страница 200: ...System Setup and Setpoints 4 4 89 Figure 4 93 ISSLogic Function Dialog Screen ...
Страница 207: ...M 4272 Instruction Book 4 96 This Page Left Intentionally Blank ...
Страница 214: ...Declaration of Conformity Appendix I I 1 IAppendix I Declaration of Conformity ...
Страница 215: ...M 4272 Instruction Book I 2 This Page Left Intentionally Blank ...