System Setup and Setpoints – 4
4–39
COMMON FUNCTION SETTINGS INPUTS TAB
Path:
System/Setup/Setpoints/Common Settings/Input
Figure 4-35, illustrates the MBTS Common Function
Settings found under the Inputs Tab on the Common
Function Settings dialog screen.
Common Settings/Breaker Status Inputs
The Breaker Status Inputs
section provides the
user with the ability to select the type of 52 breaker
status contact being used for Source 1 and Source
2. One of the three choices presented must be
selected, the 52a, or 52b or both 52a and 52b. Only
one choice for each breaker can be selected. The
selection must match the physical connections to
the unit for proper operation.
The 52a and 52b breaker status input contacts
need to be breaker auxiliary contacts that change
state whenever the breaker closes/opens and when
the breaker is in test or fully racked-in (connected)
positions. During commissioning, when a bus
transfer test is simulated, the M-4272 needs to see
the 52a and 52b contacts change state even when
the breaker is in test position.
Figure 4-35 Common Function Settings Inputs Dialog Screen
Содержание M-4272
Страница 1: ...Instruction Book Book 1 of 2 M 4272 Motor Bus Transfer System ...
Страница 45: ...xviii M 4272 Instruction Book This Page Left Intentionally Blank ...
Страница 198: ...System Setup and Setpoints 4 4 87 Figure 4 92 TCM Trip Circuit Monitor Inputs Outputs Selection Dialog Screen ...
Страница 200: ...System Setup and Setpoints 4 4 89 Figure 4 93 ISSLogic Function Dialog Screen ...
Страница 207: ...M 4272 Instruction Book 4 96 This Page Left Intentionally Blank ...
Страница 214: ...Declaration of Conformity Appendix I I 1 IAppendix I Declaration of Conformity ...
Страница 215: ...M 4272 Instruction Book I 2 This Page Left Intentionally Blank ...