M-4272 Instruction Book
4–20
Number of
Partitions
Number of Cycles
per Each Partition
1
124 Cycles
2
80 Cycles
3
60 Cycles
4
48 Cycles
5
40 Cycles
6
32 Cycles
7
28 Cycles
8
24 Cycles
9
24 Cycles
10
20 Cycles
11
20 Cycles
12
16 Cycles
13
16 Cycles
14
16 Cycles
15
12 Cycles
16
12 Cycles
Table 4-2
Recorder Partitions
NOTE
: Table 4-2 is based on 32 samples per
second. For other sample rates the
number of cycles per partition has to be
scaled accordingly.
3.
Select the desired
Trigger Inputs
and
Trigger Outputs
.
The recorder can be triggered remotely
through serial communications using
ISScom
®
, or automatically using
programmed status inputs or outputs.
4.
Select the
Post Trigger Delay
.
A post-trigger delay of 5% to 95% must
be specified. After triggering, the recorder
will continue to store data for the
programmed portion of the total record
before re-arming for the next record. For
example, a setting of 80% will result in a
record with 20% pre-trigger data, and
80% post-trigger data.
5.
Select the
Oscillograph Samples per
Cycle
.
The number of data samples per cycle
can be selected either 16 or 32 samples
per cycle.
6.
Select
Send
, ISScom will display a
Oscillograph Setup Sent Confirmation
Screen (Figure 4-16).
7.
Select
OK
, ISScom will return to the
Main Screen.
Содержание M-4272
Страница 1: ...Instruction Book Book 1 of 2 M 4272 Motor Bus Transfer System ...
Страница 45: ...xviii M 4272 Instruction Book This Page Left Intentionally Blank ...
Страница 198: ...System Setup and Setpoints 4 4 87 Figure 4 92 TCM Trip Circuit Monitor Inputs Outputs Selection Dialog Screen ...
Страница 200: ...System Setup and Setpoints 4 4 89 Figure 4 93 ISSLogic Function Dialog Screen ...
Страница 207: ...M 4272 Instruction Book 4 96 This Page Left Intentionally Blank ...
Страница 214: ...Declaration of Conformity Appendix I I 1 IAppendix I Declaration of Conformity ...