![BECKWITH ELECTRIC M-4272 Скачать руководство пользователя страница 74](http://html.mh-extra.com/html/beckwith-electric/m-4272/m-4272_instruction-book_2719813074.webp)
1
3
A
B
C
3–3
ISScom – 3
Figure 3-5 ISScom
®
Main Screen
Local is defined as originating from the HMI of the
MBTS or the RS-232 port COM1 on the front panel.
This setting prevents a transfer from being initiated
remotely when personnel are on-site “Locally”
operating the MBTS. Remote communications is
still possible and all the status information can still
be read, only manual transfer initiate control and
settings changes are blocked. When in Local control
the state of this selection cannot be changed
remotely, this means someone cannot remotely
change back to Remote Control. However, the
Remote/Local selection can always be changed
locally, personnel on-site have priority. If Remote
Control is selected, then manual transfers can be
initiated either remotely or locally. This applies to
manually initiated transfers. The Automatic Transfer
can still be initiated by internal undervoltage initiate,
ISSlogic
®
, 86P-S1 Initiate, 86P-S2 Initiate, 27-S1 or
27-S2 initiates. The Automatic Transfer operates
independently from Remote/Local control.
Device ON/OFF
The Device ON/OFF button opens a dialog screen
(Figure 3-4), that provides a selection between
“Device ON” and “Device OFF”. If “Device OFF” is
selected, then the MBTS is placed in a lockout
condition and no transfers can be executed either
remotely, locally, automatically or manually.
Monitoring of all status conditions with ISScom is
still possible, either locally (HMI or COM1) or remotely
in “Device OFF” state. The “Device ON” selection
allows normal operation.
Figure 3-4 Device On/Off Dialog Box
Содержание M-4272
Страница 1: ...Instruction Book Book 1 of 2 M 4272 Motor Bus Transfer System ...
Страница 45: ...xviii M 4272 Instruction Book This Page Left Intentionally Blank ...
Страница 198: ...System Setup and Setpoints 4 4 87 Figure 4 92 TCM Trip Circuit Monitor Inputs Outputs Selection Dialog Screen ...
Страница 200: ...System Setup and Setpoints 4 4 89 Figure 4 93 ISSLogic Function Dialog Screen ...
Страница 207: ...M 4272 Instruction Book 4 96 This Page Left Intentionally Blank ...
Страница 214: ...Declaration of Conformity Appendix I I 1 IAppendix I Declaration of Conformity ...
Страница 215: ...M 4272 Instruction Book I 2 This Page Left Intentionally Blank ...