System Setup and Setpoints – 4
4–23
4.2
System Setup
NOTE
: Setup Record Forms are contained in
Appendix A
. The Setup Record Form
tables list the MBTS parameter settings
choices for each feature and function.
The System Setup consists of defining all pertinent
information regarding the system quantities. The
Setup System dialog screen (Figure 4-20) is
accessed through the
System
menu (
System/Setup/
Setup System)
. Regardless of the functions that
are enabled or disabled, all Setup System values
are required to be entered. Several MBTS functions
require the proper setting of these values for correct
operation.
MBTS Setup System
The Nominal Frequency of 50 or 60 Hz and the CT
Secondary Rating (1 or 5 Amp) has been configured
at the factory and is indicated (grayed out and can
not be changed). However, when an ISScom
®
“New
File“ is opened, the Nominal Frequency and CT
Secondary Rating may be selected. Attempting to
write a file to an MBTS that is not configured the
same, will result in ISScom returning an error
message.
NOTE
: Communication must be established with
the target MBTS for this procedure.
To setup the MBTS System perform the following:
1.
From the ISScom Main Screen menu
select
System/Setup/Setup System
.
ISScom will display the Setup System
screen (Figure 4-20).
NOTE
: See Section 4.3, System Diagrams for
Typical VT Three-Line Connection
Diagrams.
2.
Enter the Nominal Voltage.
The Nominal Voltage setting (50 to 140 V)
is needed for proper normalization of per
unit quantities. Nominal Voltage for the
following voltage connections is as follows:
•
Line-to-Line VT connections
V
Nominal
= V Bus / VT Ratio
•
Line-to-Ground VT connections
V
Nominal
= V
Bus / (
e
3 VT Ratio)
3.
Enter the Nominal Current. The
secondary CT current of the phase CTS.
4.
Select the Phase Rotation.
(ABC or
ACB).
NOTE
: See Section 4.3,
System Diagrams
for
Typical VT Three-Line Connection
Diagrams.
5.
Select the
S1/S2 VT Configuration
button. ISScom displays the
S1/S2 VT
Configuration selection screen (Figure
4-21).
The S1/S2 VT Configuration allows the
selection of the Source 1 and Source 2
voltage transformer configuration. When
phase-ground (three-phase) is selected,
the phase-to-phase single phase choices
are grayed out and only one phase to
ground choice can be made. When phase-
to-phase (three-phase) is selected, the
phase-to-ground single-phase choices are
grayed-out and only one phase-to-phase
choice can be made. Both Source 1 and
Source 2 must have the same VT
Configuration.
6.
Select the desired S1 and S2 VT
Configuration, then select
OK
, ISScom
returns to the Setup System screen.
7.
Select the
Bus VT Configuration
button.
ISScom displays the
Bus VT Configuration
selection screen (Figure 4-23).
Some selections are grayed-out depending
on the Source 1/Source 2 selection. The
Bus VT Configuration must have the same
phase-to-ground or phase-to-phase
selection as the Source 1/Source 2
configuration. If either of three-phase
selections are chosen for the Source 1/
Source 2, then the bus must have the
same configuration. However, if the Source
1/Source 2 single-phase selection is chosen
then the bus configuration can be either
the same single-phase or the three-phase.
For example, if the Source 1/Source 2
selection is phase-to-phase (three phase),
then the bus must use the same phase-to-
phase (three-phase) configuration. If the
Source 1/Source 2 selection is phase-to-
phase (single phase BC), then the bus
choices will be phase-to-phase (single phase
BC) or phase-to-phase (three phase).
8.
Select the desired Bus VT Configuration,
then select
OK
, ISScom will return to
the Setup System screen.
Содержание M-4272
Страница 1: ...Instruction Book Book 1 of 2 M 4272 Motor Bus Transfer System ...
Страница 45: ...xviii M 4272 Instruction Book This Page Left Intentionally Blank ...
Страница 198: ...System Setup and Setpoints 4 4 87 Figure 4 92 TCM Trip Circuit Monitor Inputs Outputs Selection Dialog Screen ...
Страница 200: ...System Setup and Setpoints 4 4 89 Figure 4 93 ISSLogic Function Dialog Screen ...
Страница 207: ...M 4272 Instruction Book 4 96 This Page Left Intentionally Blank ...
Страница 214: ...Declaration of Conformity Appendix I I 1 IAppendix I Declaration of Conformity ...
Страница 215: ...M 4272 Instruction Book I 2 This Page Left Intentionally Blank ...