System Setup and Setpoints – 4
4–67
FUNCTION SETTINGS
Path:
System/Setup/Setpoints
The Function Settings Group (Figure 4-33) includes
following functions:
•
27B Bus Phase Undervoltage
•
50S1 Source 1 Instantaneous Phase
Overload Detection
•
50S2 Source 2 Instantaneous Phase
Overload Detection
•
50BF#1 Source 1 Breaker Failure
•
S1BF Source 1 Breaker Failure (Breaker
Status)
•
81 Bus Voltage Frequency
•
TCM Trip Circuit Monitor
•
60FL Bus VT Fuse-Loss
•
50BF#2 Source 2 Breaker Failure (Breaker
Status)
•
S2BF Source 2 Breaker Failure (Breaker
Status)
•
81R ROCOF (Bus Voltage)
•
CCM Close Circuit Monitor
•
ISSL ISSlogic
27B BUS PHASE UNDERVOLTAGE
Path:
System/Setup/Setpoints/27B
The 27B Bus Phase Undervoltage selection from
the Function Settings group (Figure 4-33) opens the
Bus Phase Undervoltage Transfer Initiate (S1 to
S2) dialog screen (Figure 4-67). The dialog screen
includes the following tabs:
•
27#1
Bus Phase Undervoltage Transfer
Initiate (S1 to S2)
•
27#2
Bus Phase Undervoltage Transfer
Initiate (S2 to S1)
•
27#3 Bus Phase Undervoltage
•
27#4 Bus Phase Undervoltage
27#1 BUS PHASE UNDERVOLTAGE TRANSFER
INITIATE (S1 TO S2)
Path:
System/Setup/Setpoints/27B/27#1
Figure 4-67 displays the settings for the
27#1
Bus
Phase Undervoltage Transfer Initiate (S1 to S2)
function.
Enable/Disable
— The top right corner of the display
includes a command button that will disable or enable
the function. This selection allows the
27#1
Bus
Phase Undervoltage Transfer Initiate (S1 to S2) to
be disabled (or enabled) independent from the
27#2
Bus Phase Undervoltage Transfer Initiate (S2 to S1),
27#3 Bus Phase Undervoltage or the 27#4 Bus
Phase Undervoltage.
Pickup
— The 27#1
Bus Phase Undervoltage
Transfer Initiate (S1 to S2) function Pickup (5 to
120 Volts) initiates a transfer from Source 1 to
Source 2 based on an undervoltage condition on the
motor bus. However, it can be programmed to
operate any available output.
Voltage Inhibit
— When enabled, the Voltage Inhibit
(5 to 120 Volts) is used to block the 27B Function
when the motor bus voltage is below this setting.
Voltage Inhibit is needed when the MBTS is initially
energized or when the bus phase voltage is
temporarily not applied to the unit. The Voltage
Inhibit Function may be disabled or enabled.
The 27B#1 Function settings used to initiate an
Automatic Transfer must be coordinated with any voltage
dip that may occur when large motors are started. The
27B#1 Function should not initiate a transfer when a
large motor is being started. The voltage dip caused by
a large motor starting can be as much as 10 volts and
last from several seconds up to 3 or 4 seconds.
Time Delay
— A Time Delay (1 to 8160 cycles) can
be applied to delay the Bus Phase Undervoltage
Transfer Initiate (S1 to S2) start.
I/O Selection
— The I/O Selection
button opens
the
27B#1 Bus Phase Undervoltage Transfer Initiate
Inputs/Outputs Selection Dialog Screen (Figure 4-68)
that allows any input or the Fuse Loss (FL) function
to be selected to block the 27B#1 function. The
27B#1 function can also be used to activate a
selected output when it times out.
Save/Cancel
— The Save selection saves the 27
Bus Phase Undervoltage settings either to an open
file or to the target MBTS. Cancel, returns the user
to the previous open screen.
27#2 BUS PHASE UNDERVOLTAGE TRANSFER
INITIATE (S2 TO S1)
The 27B#2 Bus Phase Undervoltage Transfer Initiate
(S2 to S1) is used to initiate a transfer from Source
2 to Source 1 based on an undervoltage condition
on the motor bus. In all other respects it is the same
as the 27B#1.
27#3 and 27#4 Bus Phase Undervoltage
The 27B#3 and 27B#4 are general purpose Bus
Phase Undervoltage functions. They have the same
settings and I/O selections as 27B#1 and 27B#2
except they are
not
predefined to initiate transfers.
These functions could be used for load shedding,
tripping or as an alarm.
Содержание M-4272
Страница 1: ...Instruction Book Book 1 of 2 M 4272 Motor Bus Transfer System ...
Страница 45: ...xviii M 4272 Instruction Book This Page Left Intentionally Blank ...
Страница 198: ...System Setup and Setpoints 4 4 87 Figure 4 92 TCM Trip Circuit Monitor Inputs Outputs Selection Dialog Screen ...
Страница 200: ...System Setup and Setpoints 4 4 89 Figure 4 93 ISSLogic Function Dialog Screen ...
Страница 207: ...M 4272 Instruction Book 4 96 This Page Left Intentionally Blank ...
Страница 214: ...Declaration of Conformity Appendix I I 1 IAppendix I Declaration of Conformity ...
Страница 215: ...M 4272 Instruction Book I 2 This Page Left Intentionally Blank ...