M-4272 Instruction Book
4–52
Automatic Delayed In-Phase Transfer/Blocking
Inputs Selection
The Blocking Inputs Selection
button opens the
Blocking Inputs Selection dialog screen (Figure
4-50). Any Input or the Fuse Loss (FL) function can
be selected to block a Delayed In-Phase Transfer.
When other functions such as External Status Reset
are selected for these inputs it will be identified next
to that input.
Automatic Delayed In-Phase Transfer Save/
Cancel
The Save selection saves the Automatic Delayed
In-Phase Transfer Tab settings either to an open
file or to the target MBTS. Cancel, returns the user
to the previous open screen.
The conditions that are necessary to execute a
Delayed In-Phase Transfer are:
•
No Lockout/Blocking conditions exist.
•
The conditions for Fast Transfer have not
been matched.
•
The Delta Voltage between the motor bus
and the new source is within limit setting.
•
The Delta Frequency between the motor
bus and the new source is within limit
setting.
•
The Phase Angle between the motor bus
and the new source is changing and must
enter the first phase coincidence (first
zero degree crossing) within the Delayed
In-Phase Transfer time window (adjustable
from 10 to 600 cycles).
The Delayed In-Phase Transfer feature
includes two programmable advanced
breaker closing times for Source 1 and
Source 2 breakers (Figure 4-35) to
coordinate the closing of the first phase
coincidence. Programmable breaker
closing time is from 0 to 12 cycles.
AUTOMATIC TRANSFER SETTINGS/RESIDUAL
VOLTAGE TRANSFER TAB
Path:
System/Setup/Setpoints/Automatic Transfer
Settings/Residual Voltage Transfer
Figure 4-52, illustrates the MBTS Automatic Transfer
Settings found under the Residual Voltage Transfer
Tab on the Automatic Transfer Settings dialog
screen.
Figure 4-52 Automatic Transfer Settings Residual Voltage Transfer Tab Dialog Screen
Содержание M-4272
Страница 1: ...Instruction Book Book 1 of 2 M 4272 Motor Bus Transfer System ...
Страница 45: ...xviii M 4272 Instruction Book This Page Left Intentionally Blank ...
Страница 198: ...System Setup and Setpoints 4 4 87 Figure 4 92 TCM Trip Circuit Monitor Inputs Outputs Selection Dialog Screen ...
Страница 200: ...System Setup and Setpoints 4 4 89 Figure 4 93 ISSLogic Function Dialog Screen ...
Страница 207: ...M 4272 Instruction Book 4 96 This Page Left Intentionally Blank ...
Страница 214: ...Declaration of Conformity Appendix I I 1 IAppendix I Declaration of Conformity ...
Страница 215: ...M 4272 Instruction Book I 2 This Page Left Intentionally Blank ...