M-4272 Instruction Book
2–8
3.
If Level Access is not active, then the
following is displayed:
INIT TRANSFER
INIT
rmte_lcal
4.
Verify that the
Transfer Ready (
Status
Module) indicator is Green.
5.
If the
Transfer Ready (
Status Module)
indicator is not Green, then clear the
condition(s) blocking the transfer.
6.
Verify the HMI display indicates the
following:
INIT TRANSFER
INIT
rmte_lcal
7.
Press
ENTER,
the following will be
displayed:
INIT MANUAL TRANSFER?
yes NO
8.
Press the Left arrow pushbutton once to
select
YES
.
9.
Initiate a Manual transfer by pressing
ENTER
. The following will be displayed:
INIT TRANSFER
INIT
rmte_lcal
10.
If the Manual Transfer cannot be
completed, then
INCOMP TRANS
BLOCK
will be illuminated on the Status
Module.
The MBTS is blocked from performing
another transfer until reset.
11.
If the MBTS completes the Manual
Transfer successfully, then the following
will be indicated:
Status Module
•
What type of transfer was completed
•
Close S1(S2) Breaker
•
Trip S2(S1) Breaker
Front Panel LEDs
•
S2(S1) Breaker Closed LED
•
S1(S2) Breaker Opened LED
HMI will display (scroll) the following
screens:
MANUAL FAST TRANSFER
08-NOV-2005
10:11:49.948
MANUAL FAST TRANSFER
--OUTPUTS--
MANUAL FAST TRANSFER
04
01
MANUAL FAST TRANSFER
--PICKUP ELEMENTS--
MANUAL FAST TRANSFER
--OPERATE ELEMENTS--
12.
Press and release the
Status Reset
pushbutton to reset the status indicators.
Remote/Local Control
The Remote/Local selection feature provides control
of the MBTS from Local mode (COM1 or HMI) and
remote mode (COM2, RS485, Ethernet or external
input). Remote/Local feature is configured from Local
mode (COM1 or HMI) only.
When Local mode is selected manually, initiated
transfers or settings changes through the COM1 or
HMI are allowed. Any Remote manually initiated
transfers or settings changes of the MBTS is blocked.
When Remote mode is selected manually, initiated transfers
or settings changes through the COM1, HMI, COM2,
RS485, Ethernet or external input is allowed.
Remote/Local Control (ISScom)
To switch Control Method utilizing ISScom
®
perform
the following:
Q
NOTE
: Communication must be established with
the target MBTS for this procedure.
1.
From the ISScom Main Screen menu bar
select
Remote/Local
. ISScom will display
the Remote/Local Mode dialog screen
(Figure 2-6).
Figure 2-6 Remote/Local Mode Dialog Screen
Содержание M-4272
Страница 1: ...Instruction Book Book 1 of 2 M 4272 Motor Bus Transfer System ...
Страница 45: ...xviii M 4272 Instruction Book This Page Left Intentionally Blank ...
Страница 198: ...System Setup and Setpoints 4 4 87 Figure 4 92 TCM Trip Circuit Monitor Inputs Outputs Selection Dialog Screen ...
Страница 200: ...System Setup and Setpoints 4 4 89 Figure 4 93 ISSLogic Function Dialog Screen ...
Страница 207: ...M 4272 Instruction Book 4 96 This Page Left Intentionally Blank ...
Страница 214: ...Declaration of Conformity Appendix I I 1 IAppendix I Declaration of Conformity ...
Страница 215: ...M 4272 Instruction Book I 2 This Page Left Intentionally Blank ...