• If the Link Status indicates that there is no link, please inspect the wiring, and verify that your Ethernet switch is powered up.
• If the link parameters are not as expected (wrong baud rate or duplex) try the following:
• Log into your managed switch and verify that the port to which iVu camera is connected is correctly configured. Alternatively,
consult with your IT person to perform this verification.
• Verify that your cable is of the right type, and is properly connected to the switch and to the camera.
9.8.2 Networking and TCP/IP Diagnostics
To verify networking and TCP/IP connectivity, follow these steps:
• Verify that the Ethernet link has been established.
• Visit the System > Communications > Ethernet I/O page, and examine the sensor IP address, subnet mask, and the Gateway
address:
• Verify with your IT person that these settings are correct.
• If necessary, make the required modifications and reboot the sensor
• Press the Status button on the same page, and go to the Ethernet I/O Status page:
• On the PC attached to your LAN, open the Command window. To do this, press Start > Run, and then type in
cmd and press the OK
button.
• A command window will be displayed:
iVu Plus BCR User's Manual
142
www.bannerengineering.com - tel: 763-544-3164
Rev. B
Содержание iVu Plus BCR
Страница 1: ...iVu Plus BCR User s Manual Rev B 1 25 2012...
Страница 56: ...iVu Plus BCR User s Manual 56 www bannerengineering com tel 763 544 3164 Rev B...
Страница 58: ...Main Menu Imager Exposure iVu Plus BCR User s Manual 58 www bannerengineering com tel 763 544 3164 Rev B...
Страница 64: ...iVu Plus BCR User s Manual 64 www bannerengineering com tel 763 544 3164 Rev B...
Страница 104: ...iVu Plus BCR User s Manual 104 www bannerengineering com tel 763 544 3164 Rev B...
Страница 105: ...2 Select Module iVu Plus BCR User s Manual Rev B www bannerengineering com tel 763 544 3164 105...
Страница 155: ...T Touchscreen Calibration 34 U USB loading from 24 saving to 24 Rev B www bannerengineering com tel 763 544 3164 155...