C.5.3b Pipe OD
4. Click on the appropriate
pipe OD
unit type in the
center pane from the list shown in
Table 17
below.
Then enter the known pipe outside diameter or
circumference in the right pane and click [next item].
Obtain the required information by measuring either
the pipe outside diameter (OD) or circumference at the
transducer installation site. The data may also be obtained
from standard pipe size tables found in
Sound speeds and
pipe size data
(914-004).
Table 17: Available pipe OD units
English
Metric
inch
mm
feet
meters
circum.in = pipe
circumference in inches
circum.mm = pipe
circumference in
millimeters
circum.ft = pipe
circumference in feet
circum.m = pipe
circumference in meters
5. Enter the known
pipe wall
thickness (in inches or mm)
in the right pane and click [next item].
C.5.3c Path and axial lengths
6. Click on the appropriate
path length
unit type in the
center pane. Then enter the path length of the ultrasonic
signal in the right pane and click [next item].
NOTE:
If a spoolpiece was ordered with the meter, the
transducer signal path length (P) and the transducer
signal axial length (L) are engraved on the flowcell
and/or are included in the documentation supplied
with the meter. For on-site transducer installations,
refer to
Appendix C, Measuring P and L dimensions
,
in the
Startup guide
for instructions.
7. Click on the appropriate
axial length
unit type in t
he center pane. Then enter the axial length of the
ultrasonic signal in the right pane and click [next item].
C.5.3d Fluid type
8. Double-click on the appropriate
fluid type
, either
air
or
other
.
• If you select
other
, PanaView asks for the
fluid
soundspeed
. Enter the appropriate soundspeed
(in ft/sec) and click [next item].
C.5.3e Reynolds Correction
9. Double-click on the appropriate choice to indicate
whether you want
Reynolds Correction
.
• If
off
is selected, enter the
calibration factor
and click on [next item].
• If
on
is selected, enter the
kinematic viscosity
and
click [next item]. Then enter the
calibration factor
and click [next item].
PanaView returns to the channel
program
menu.
You have completed entering pipe parameters.
59
Содержание DigitalFlow XGF868i
Страница 1: ...DigitalFlow XGF868i Panametrics flare gas flow transmitter Programming manual...
Страница 2: ...ii...
Страница 4: ...no content intended for this page iv...
Страница 10: ...x...
Страница 38: ...28...
Страница 46: ...no content intended for this page 36...
Страница 54: ...44...
Страница 60: ...50...
Страница 88: ...78...
Страница 94: ...84...