background image

Open the Device

Before opening the device, remove it from the field and operating environment.

 

To prevent damage to the O-rings, turn the e-module retaining ring counter-clockwise ½ to one 

turn, and then clockwise about ¼ turn, and repeat until you can remove the retaining ring. 

If you experience difficulty removing the retaining ring, the e-module may be rotating with the 

retaining ring. Turn the retaining ring clockwise slightly and press down lightly on the e-module 

to hold it in place. Then turn the retaining ring counter-clockwise. 

Clean the Interior

To clean the interior, remove the components.

 

l

Remove the e-module at top. Press upward lightly on the side 

opposite the module’s contact pins. 

 

l

Remove the battery using the battery installation tool.

 

l

To clean the interior, use a clean, dry, anti-static cloth.

Inspect the O-rings

The Ranger Pro device uses two O-rings to seal the unit against dust 

and moisture. 

34x1mm O-ring on the e-module

35x1mm O-ring on the case

To maintain the device's IP67 dust and water-resistant rating 

and prevent leaks, you must install and lubricate the O-rings 

properly.

To inspect the O-rings:  

 

l

Verify that the O-rings are free from dust and debris.

 

l

To remove dust and dirt, use a clean, dry cloth.

 

l

When you install new O-rings, coat them very lightly with 

silicone grease. 

If they’re damaged, or if you're replacing the battery, always replace the O-rings. For details and 

ordering information, see the 

Ranger Pro Datasheet

  (document 125M5237) available from 

Bently.com

.

46/56

Ranger Pro Wireless Condition Monitoring Device
User Guide

125M6113 Rev. D

Содержание Bently Nevada Ranger Pro

Страница 1: ...Ranger Pro Wireless Condition Monitoring Device User Guide Bently Nevada Machinery Condition Monitoring 125M6113 Rev D...

Страница 2: ...s any and all liability for any direct indirect consequential or special damages claims for lost profits or third party claims arising from the use of the information whether a claim is asserted in co...

Страница 3: ...and Configuration 16 4 1 Install Battery 16 4 2 Configure Network 20 4 3 Provision Devices 20 4 4 Unprovision Devices 26 4 5 Reboot the Device 28 4 6 Configure Devices 29 4 7 Install and Configure Sys...

Страница 4: ...procedures The format of these markings are governed by the standards that dictate safe use and environmental compliance in a variety of regions and regulated settings More specific product safety war...

Страница 5: ...use it to fail or in hazardous locations cause other unintended consequences Lithium batteries are volatile When handling and storing lithium metal batteries follow these precautions l Store and handl...

Страница 6: ...amounts within the system Recycling Facilities Decommissioning of instrumentation should endeavor to minimize the impact of the waste created by disposal of system components Refer to local or regiona...

Страница 7: ...Description The Ranger Pro ISA100 11a wireless sensor measures temperature acceleration and velocity Ranger Pro sensors detect acceleration using piezoelectric ceramic sensing elements in the sensor b...

Страница 8: ...ou to extend the range between sensors and network access points For ISA100 networks both the tri axial and uniaxial sensors can also act as routers although using the router mode depletes the unit s...

Страница 9: ...s adapters if needed l A compatible USB NFC reader Contact Bently Nevada technical support for a list of compatible readers l Ranger Pro Configuration Software 121M7997 available from Bently Nevada te...

Страница 10: ...can purchase approved batteries from Bently Nevada or third party suppliers For details and ordering information see the Ranger Pro Datasheet document 125M5237 Network Requirements Ranger Pro devices...

Страница 11: ...WirelessHART Network requirements Manufacturer Gateway Router Emerson Wireless 1410 1420 Gateway 4 7 84 or later N A 11 56 Ranger Pro Wireless Condition Monitoring Device User Guide 125M6113 Rev D...

Страница 12: ...etwork 3 1 Consider Sensor Range A sensor can transmit data up to 150 meters 164 yards to an access point when unimpeded by environmental influences A sensor can optimally transmit data to another sen...

Страница 13: ...west reasonable measurement interval to monitor vibration and temperature More frequent vibration measurements consume more power For example changing the interval from 30 to 10 minutes reduces batter...

Страница 14: ...e nominal radio frequency range around the proposed location of each Ranger Pro device When connecting to a backbone router or access point the range is about 50 greater When the device is placed amon...

Страница 15: ...Repeaters ought to be positioned o Relatively high above the sensors preferably at least two meters 6 feet above grade Higher placement dramatically increases signal strength o To improve radio freque...

Страница 16: ...o Warning Special Conditions and Additional Information 126M6550 available from Bently com To maintain the device s IP67 dust and water resistant rating assemble the device carefully To install a batt...

Страница 17: ...slight radial force and push upward until the e module is separated from the case 3 Use the battery installation tool to remove the battery retaining ring Turn the ring counter clockwise Use the magn...

Страница 18: ...install and lubricate the O rings properly 5 Inspect the interior threads of the e module retaining ring to be sure they aren t damaged 6 Verify that the positive end of the battery is up and then in...

Страница 19: ...e sensor in place with your finger Inspect the exterior threads of the sensor case as well as the interior threads of the e module retaining ring to be sure they are not damaged 10 Align the e module...

Страница 20: ...Ranger Pro configuration software functions include l Device provisioning l Rebooting the device l Unprovisioning l Device configuration including l Applying default configurations l Saving loading an...

Страница 21: ...Provision Using a USB NFC Reader on page 1 l WirelessHART gateway see Provision Using a USB NFC Reader on page 1 If a Ranger Pro device does not join the network it may be in a sleep state It periodic...

Страница 22: ...ice Role as IO IO Auto or IO Router d If applicable Select the Primary Router e If applicable Select the Secondary Router 3 Click Download to apply the updated configuration to the gateway When succes...

Страница 23: ...Periodic Periodic Publication period 0 zero 150 150 Stale limit Default 5 5 Retry mode Normal Normal Normal 8 For each type of Ranger Pro device verify these additional Concentrator OID 11 Read Parame...

Страница 24: ...ampling Data The Sampling Data pane is displayed c Click Edit The Sampling Settings dialog box is displayed d Verify that the firmware version CF file version and OID parameters are correct for the de...

Страница 25: ...Provision 8 Click Enable for 60 Minutes Wait for the unprovisioned devices to display in the Property Panel This may take five to ten minutes 9 Select the un provisioned devices and click Accept 10 I...

Страница 26: ...o obtain drivers visit the website of the NFC reader vendor 4 Select the appropriate USB NFC reader in the NFC Manager tab header 5 Place the Ranger Pro device upside down on the USB NFC reader pad 6...

Страница 27: ...ted and its status is changed to out of service OOS 6 In the tool bar click Provisioning Delete The Delete Devices dialog box is displayed 7 Select the device s you previously inactivated 8 Click Dele...

Страница 28: ...ese steps for ISA100 devices the Ranger Pro device is unprovisioned disconnects from the network and is ready to be provisioned for the same or a new ISA100 network Although not required when changing...

Страница 29: ...ng two modes Live Configuration l View modify and update sensor configurations in real time l Most often used to change device configuration on a single device Preset Configuration l View modify save...

Страница 30: ...sors pane displays all devices and their status If using System 1 to modify the gateway IP address refer to the System 1 online help or user guide Configure Sensors Over the Network To configure senso...

Страница 31: ...d preset configuration data 7 Select the Ranger Pro device s to which you want to apply the preset configuration To select multiple devices press CTRL or SHIFT 8 In Network Manager Sensors click Apply...

Страница 32: ...ls for the new units to take effect For ranges and complete specifications see the Ranger Pro Datasheet document 125M5237 Advanced Settings After you connect to a gateway you can view device settings...

Страница 33: ...nder these compatibility guidelines You must upgrade the System 1 Ranger Pro plugin before you upgrade device firmware If you upgrade device firmware first System 1 may decommission the installed devi...

Страница 34: ...e Ranger Pro plugin from the Bently Nevada Flexera licensing server 7 Install the plugin 8 Open the System 1 database 9 Enable data collection 10 If needed Wait for the Configuration Out of Date messa...

Страница 35: ...o use a We recommend you drill and tap a mounting hole o Verify that the machine housing is suitable for drilling a mounting hole o Refer to the machine warranty or other documentation o Consider the...

Страница 36: ...chine at the mounting point o On curved surfaces use a spot facing tool to provide a flat mounting surface o Use a steel wire brush to remove all paint from the mounting surface 2 Prepare the attachme...

Страница 37: ...62 in lb 6 Optional Secure the device by passing a 1mm 04 inch lanyard not provided by Bently Nevada through the fall protection hole in the base Secure the lanyard to a suitable retaining point 37 5...

Страница 38: ...rk connection Dismount the device from the machine and position it closer to an access point or router l If possible improve the device s radio frequency communication by relocating it or reorienting...

Страница 39: ...t be less than 50 and preferably less than 20 5 2 Validate Device Data Depending on the wireless management system you are using there are several ways to validate that each device is transmitting dat...

Страница 40: ...inches s RMS X 5 Y 5 Z 5 X 1000 Y 1000 Z 1000 PeakDemod Overall Enabled N A Peak N A N A Dynamic Data Dynamic data is measured at the interval and start date time set by the user You can select the nu...

Страница 41: ...r to CF file release notes for details on configuring single tri axial and repeater AIO objects Devices use firmware version 02 01 02 02 or later Byte Order Little Endian 32 bit Data type float l CH01...

Страница 42: ...CC 1 SV Secondary Variable HartTag Z OVL VEL 2 TV Tertiary Variable HartTag Z PK DEMOD 3 QV Quartenary Variable HartTag X OVL ACC 4 N A HartTag X OVL VEL 5 N A HartTag X OVL ACC 6 N A HartTag X OVL VE...

Страница 43: ...For details and ordering information see the Ranger Pro Datasheet document 125M5237 available from Bently com Battery Status Monitoring Battery status is updated once per hour and may be trended Batt...

Страница 44: ...sits from the exterior of the sensor use an electronic contact or switch cleaner Diagnose Device Status If a device fails use the NFC reader to identify the fault The NFC reader displays additional de...

Страница 45: ...legacy model Read Fault Diagnostics The sensor diagnostics data could not be read Bypass Diagnostics The sensor diagnostics data was successfully read but the model has been detected as a legacy mode...

Страница 46: ...pins l Remove the battery using the battery installation tool l To clean the interior use a clean dry anti static cloth Inspect the O rings The Ranger Pro device uses two O rings to seal the unit aga...

Страница 47: ...n the inside and at the bottom of the sensor module Inspect the Battery Inspect the battery before removing it Look for l Swelling deformation or elongation l Indentations or lifting of battery termin...

Страница 48: ...Over the air As you upgrade the firmware monitoring may be interrupted When the firmware update is complete the Ranger Pro device restarts All nodes connected to the device are temporarily disconnect...

Страница 49: ...e sensor firmware be sure you have downloaded and added current versions of the firmware to the application To update firmware using the Bently Nevada Ranger Pro ISA100 gateway 1 Verify that all Range...

Страница 50: ...or Firmware dialog box is displayed 8 Do not modify TSAP and Object ID default values Click the Firmware file browse button The Open dialog box is displayed 9 Navigate to the location of the firmware...

Страница 51: ...Select it and click Open The DD is listed in the dialog box 7 Click Close To update firmware using a Honeywell OneWireless Device Manager 1 Verify that all Ranger Pro devices are provisioned connected...

Страница 52: ...ay hosting the sensors you want to update 4 Select the Firmware tab 5 Select a valid firmware version and click Upgrade 6 Select Network Manager Sensors tab 7 Update progress is displayed in the Firmw...

Страница 53: ...vidually update the e module firmware 1 Open the Ranger Pro Configuration Software 2 Connect the NFC reader to the computer running the Ranger Pro Configuration Software 3 Place the Ranger Pro device...

Страница 54: ...nrecognized The sensor identification data was successfully read but the model is not recognized Model Unsupported The sensor identification data was successfully read but the model is not supported B...

Страница 55: ...e sensor firmware Update Radio Firmware Using Honeywell Gateway With one exception the process to upgrade a Ranger Pro device radio firmware on a Honeywell gateway is the same as upgrading the sensor...

Страница 56: ...eaders l Verify that the latest firmware is installed on all NFC readers and device e modules and sensors l Follow your site s standards or industry s best practices for strong passwords l Only instal...

Отзывы: