Modbus Settings
The Ranger Pro sensors publish vibration and temperature (process variable data) values as 32-
bit, floating point data. You can output Ranger Pro static data like vibration and temperature
using the gateway's Modbus interface.
Phase 1 Ranger Pro Devices
Devices use firmware version 01.01.06.03 or earlier.
Byte Order
: Little Endian, 32-bit
Data type
: float
l
CH01_AI: Tagname.CH01_AI.PV = Temperature
l
CH02_AI: Tagname.CH02_AI.PV = X-Accel
l
CH03_AI: Tagname.CH03_AI.PV = X-Vel
l
CH04_AI: Tagname.CH04_AI.PV = Y-Accel
l
CH05_AI: Tagname.CH05_AI.PV = Y-Vel
l
CH06_AI: Tagname.CH06_AI.PV = Z-Accel
l
CH07_AI: Tagname.CH07_AI.PV = Z-Vel
Phase 2 Ranger Pro Devices
Refer to CF file release notes for details on configuring single, tri-axial and repeater AIO
objects.
Devices use firmware version 02.01.02.02 or later.
Byte Order
: Little Endian, 32-bit
Data type
: float
l
CH01_AI: Tagname.Temperature.PV
l
CH02_AI: Tagname.Z-Axis-Accel.PV
l
CH03_AI: Tagname.Z-Axis-Vel.PV
l
CH04_AI: Tagname.Z-Axis-PkDemod.PV
l
CH05_AI: Tagname.Y-Axis-Accel.PV
l
CH06_AI: Tagname.Y-Axis-Vel.PV
l
CH07_AI: Tagname.X-Axis-Accel.PV
l
CH08_AI: Tagname.X-Axis-Vel.PV
Phase 3 Ranger Pro WirelessHART Devices
Use these device variable IDs to map WirelessHART Ranger Pro device variables to Modbus
registers.
l
All Ranger Pro WirelessHART devices use firmware version 3.X.X.X or later.
l
Byte Order: Refer to WirelessHART network hardware vendor documentation.
l
Data type: float (4-bytes).