1. Download the CF and firmware files from
Bently Nevada technical support
2. Verify that all Ranger Pro devices are provisioned, connected to the network, and joined to
the gateway.
3. In the Yokogawa Field Wireless Management Console, open
Monitor
.
4. Choose
Tools
>
Firmware Download Manager
. The
Firmware Download Manager
dialog
box is displayed.
5. Select the
Sensor Firmware
tab. Ranger Pro devices are listed.
6. Select the check box of the devices you want to upgrade.
7. Select
Download Firmware
. The
Update Sensor Firmware
dialog box is displayed.
8. Do not modify
TSAP
and
Object ID
default values. Click the
Firmware file
browse button.
The
Open
dialog box is displayed.
9. Navigate to the location of the firmware file. Select it and click
Open
. The
Update Sensor
Firmware
dialog box is displayed.
10. Click
Start Download
. When the download is complete, the
Firmware Download Manager
dialog box is displayed and the node is highlighted Yellow.
11. In the
Sensor Firmware
tab, select the Yellow highlighted devices and click
Apply
. The
firmware upgrade is applied and the sensors are restarted.
12. Apply the Capabilities File.
See XREF Needed. TBD
50/56
Ranger Pro Wireless Condition Monitoring Device
User Guide
125M6113 Rev. D