WirelessHART Sleep State
The WirelessHART device radio listens for advertisements from the configured network for a one-
hour period at periodic intervals. This is followed by a one-hour deep sleep period, after which
the device reinitiates searching for the network as it did during the first hour. This cycle continues
until it successfully joins the network or is rebooted.
Provision Using the Yokogawa ISA100 Gateway
Before you can provision Ranger Pro devices on a Yokogawa gateway, you must first add the
devices to the network configuration.
For more information and detailed instructions, refer to the Yokogawa documentation.
Add Devices
To add devices to a Yokogawa ISA100 network:
1. In the Yokogawa
Field Wireless Management Console
, open
Configurator
.
2. Add Ranger Pro devices to the Field Wireless Network on the
Field Devices
tab.
a. Set the
Device Tag
.
b. Check
OTA Provisioning
.
c. Select the
Device Role
as
IO
,
IO Auto
, or
IO+Router
.
d. (If applicable) Select the
Primary Router
.
e. (If applicable) Select the
Secondary Router
.
3. Click
Download
to apply the updated configuration to the gateway. When successful, a
confirmation message is displayed.
Apply capabilities file
After you add the devices, provision the devices. We recommend configuring the device
Sampling Data
before provisioning devices. The capabilities file (CF) required to configure
devices is available from Bently Nevada Technical Support.
To apply a CF file to the Ranger Pro devices:
1. In the Yokogawa Field Wireless Management Console, open
Configurator
.
2. Select
Sampling Data
. The
Sampling Data
pane is displayed.
3. Click
Add
. The
Sampling Settings
dialog box is displayed.
4. In the
Device Tag
field, click browse and select the check box of the device you want to
modify. You can select multiple devices of the same type. Click
OK
.
5. In the CF / DD pane, select
CF File
. If the CF file is not yet displayed:
a. Select
Load CF/DD.
TheWindows
Open
dialog box is displayed.
22/56
Ranger Pro Wireless Condition Monitoring Device
User Guide
125M6113 Rev. D