The severity levels are:
l
Green
o
Vibration is below defined limits.
o
Data is collected at the configured interval.
l
Yellow
o
Vibration is between the lower and upper defined limits.
o
Acquire a dataset immediately.
o
Revert to collecting data at the configured interval.
l
Red
o
Vibration is above the upper defined limit.
o
Acquire a dataset immediately.
o
Set overall measurements to be taken at the shortest allowed interval (10 minutes).
o
Set dynamic measurements
4.7 Install and Configure System 1 Plugin
System 1 supports running a mixture of Ranger Pro devices running old and current versions of
the firmware under specific conditions.
Compatibility
System 1 supports Ranger Pro devices running mixed versions of firmware under these
compatibility guidelines:
You must upgrade the System 1 Ranger Pro plugin before you upgrade device firmware. If
you upgrade device firmware first, System 1 may decommission the installed devices.
System 1 Version Ranger Pro Plugin Version
Firmware Version
Compatibility
19.1 and earlier
20XXX
2.1.2.2 (ISA100)
Yes
19.1 and earlier
20XXX
2.1.2.2 (ISA100)
Not recommended
19.2 or later
30XXX
2.1.2.2 (ISA100)
Yes
19.2 or later
20XXX
3.1.x.x (ISA100 only)
No
19.2 or later
30XXX
2.1.2.2 (ISA100)
3.1.x.x (ISA100)
3.1.x.x (WirelessHART)
Yes (recommended)
New System 1 Installation
Install System 1 and the Ranger Pro plugin before adding Ranger Pro devices as follows:
1. Install System 1 version 19.1 or later and appropriate hotfix and/or service packs.
2. Download the appropriate compatible Ranger Pro plugin from the Bently Nevada Flexera
licensing server.
33/56
Ranger Pro Wireless Condition Monitoring Device
User Guide
125M6113 Rev. D