Static Process Variable Data
Process Variable (PV) or direct data is used to trend the overall vibration and temperature. PV
data can be sent to System 1 through GCI or through Modbus/OPC and conforms to ISA100,
foundation fieldbus standard. PV data is timestamped by the gateway and not at the time of
acquisition. A user can select the units, sub-units, time interval, F
min
and F
max
settings.
Measurement
Type
Default Mode Measurement
Units
Default Sub-
units
(RMS or Peak)
Default F
min
(high pass
filter
frequency)
Default F
max
(low pass
filter
frequency)
Temperature Enabled
°F, °C
N/A
N/A
N/A
Acceleration
Overall
Enabled
g, m/s^2
RMS
X: 5
Y: 5
Z: 5
X: 5000
Y: 5000
Z: 10000
Velocity
Overall
Enabled
mm/s,
inches/s
RMS
X: 5
Y: 5
Z: 5
X: 1000
Y: 1000
Z: 1000
PeakDemod
Overall
Enabled
N/A
Peak
N/A
N/A
Dynamic Data
Dynamic data is measured at the interval and start date/time set by the user. You can select the
number of samples, F
min
, F
max
, and time interval. Dynamic data is collected sequentially for each
measurement axis and time stamped when the data collection occurs.
Measurement
Type
Default Mode Measurement
Units
Default Fmin
(high pass
filter
frequency)
Default Fmax
(low pass
filter
frequency )
Other
Acceleration
Waveforms
Enabled
g, m/s^2
N/A
N/A
Measurement
samples used:
4096
Velocity
Spectrum
(rms only
sub-units)
Enabled
mm/s,
inches/s
X: 5
Y: 5
Z: 5
X: 1000
Y: 1000
Z: 1000
Lines Default
FFT Points:
1600
PeakDemod
Spectrum
(Peak only
sub-units)
Enabled
(Z axis only)
g, m/s^2
X: 5
Y: 5
Z: 5
1000
Lines Default
FFT Points:
1600
40/56
Ranger Pro Wireless Condition Monitoring Device
User Guide