Update Sensor Firmware Using Honeywell Gateway
Before you upgrade the device firmware, obtain the correct device descriptor (DD) file required
for each type of Wireless Condition Monitoring Device device from Bently Nevada
. You only need to add a DD file to the gateway once for each device type.
To add Honeywell device descriptor (DD) file to the Honeywell OneWireless Device Manager
(WDM):
1. Download the device descriptor (DD) files from
Bently Nevada technical support
2. Copy the DD zip file to the computer connected to the Honeywell OneWireless Device
Manager (WDM). Do not unzip the archives.
3. Open Honeywell WDM.
4. Select
Maintenance
>
Templates
. The
Load ISA100.11a DD / Modbus config file
dialog box
is displayed.
5. Click
Load ISA100.11a DD / Modbus file.
The Windows
Open
dialog box is displayed.
6. Navigate to the Windows directory location of the DD file. Select it and click
Open
. The DD is
listed in the dialog box.
7. Click
Close
.
To update firmware using a Honeywell OneWireless Device Manager:
1. Verify that all Ranger Pro devices are provisioned, connected to the network, and joined to
the gateway.
2. Open Honeywell OneWireless Device Manager (WDM).
3. In the
Selection Panel
, select the device you want to upgrade.
4. In the tools ribbon, click
Upgrade
and select
Application
. The
Application Firmware
Upgrade
dialog box is displayed.
5. To add a firmware file, click
Add
. The Windows
Open
dialog box is displayed.
6. Navigate to the location of the firmware file. Select it and click
Open
. The firmware is listed in
Available Firmware Files
.
7. Select the Ranger Pro device to be updated and click
Upgrade
. The firmware update is
automatically applied.
8. Refresh the list of Ranger Pro devices.
a. Delete the upgraded device(s) from Honeywell WDM.
b. Allow the device to rejoin.
9. Once loaded, Honeywell applies the correct device descriptor (DD) file to each device.
51/56
Ranger Pro Wireless Condition Monitoring Device
User Guide
125M6113 Rev. D