b. Navigate to the Windows directory location of the device compatibility file you
previously downloaded from Bently Nevada tech support. Select the capability file
matching the device you want to upgrade, as shown below.
Ranger Pro Device
Yokogawa Model
Capability File Name
70M300 Repeater
GE/70M300
BHGE-RP-70M300 v6.1.CFF
70M301 Single Axis
GE/70M301
BHGE-RP-70M301 v6.1.CFF
70M303 Tri-Axis
GE/70M303
BHGE-RP-70M303 v6.1.CFF
c. Click
Open
. The CF file is displayed in the
CF File
field.
6. Select the CF file compatible with the devices displayed in the
Device Tag
field.
7. For each type of Ranger Pro device, modify these Concentrator OID:11
Read Parameters
:
OID Concentrator
Value
70M300 Repeater
70M301 Single Axis
70M303 Tri-Axis
Update policy
Periodic
Periodic
Periodic
Publication period
0 (zero)
150
150
Stale limit
Default
5
5
Retry mode
Normal
Normal
Normal
8. For each type of Ranger Pro device, verify these additional Concentrator OID:11
Read
Parameters
:
OID Parameter
70M300 Repeater
70M301 Single Axis
70M303 Tri-Axis
UAPMO
Diag_Status
To prevent session timeout, select the
UAPMO Diag_Status
parameter (if displayed) and click the "<" button. The parameter is
moved to the list of
Available Parameters
.
AI_01 AI_02 AI_
03 AI_04 AI_05 AI_06
AI_07 AI_08
Not available
AI_01 - AI_05:
available
AI_06 - AI_8:
unavailable
AI_01 - AI_08:
available
9. For each type of Ranger Pro device, configure the Concentrator OID:12
Read Parameters
.
OID Concentrator
Value
70M300 Repeater
70M301 Single Axis
70M303 Tri-Axis
Update policy
Default
Periodic
Periodic
Publication period
Default
10
10
Stale limit
Default
10
10
Retry mode
Default
Normal
Normal
23/56
Ranger Pro Wireless Condition Monitoring Device
User Guide
125M6113 Rev. D