71
Operation
Parameter listing
Menu
Submenu
Parameter Name
Description
Range
Factory settings
42
Building Management System
42.
0 General
42.
0. 0
BMS Control Mode
0 = Disabled
1 = Voltage Power
2 = Voltage Temp
3 = Current Power
4 = Current Temp
5 = External Controller Power
6 = External Controller Temp
0 - 6
0
42.
0. 1
BMS Max Temp
°C
90
42.
0. 1
BMS Min Temp
°C
20
42.
1 Analog Level Settings
42.
1. 0
BMS Analog Control Voltage to Started Heat Demand
V
1
42.
1. 1
BMS Analog Control Voltage to Stop Heat Demand
V
0,5
42.
1. 2
BMS Analog Control Voltage for Maximum Heat Demand
V
9,5
42.
1. 3
BMS Analog Control Voltage for Minimum Heat Demand
V
2
42.
1. 4
BMS Analog Control Current to Start Heat Demand
mA
60
42.
1. 5
BMS Analog Control Current to Stop Heat Demand
mA
50
42.
1. 6
BMS Analog Control Current for Maximum Heat Demand
mA
190
42.
1. 7
BMS Analog Control Current for Minimum Heat Demand
mA
70
42.
2 Diagnostics
42.
2. 0
BMS Status
0 = Absent
1 = Disabled
2 = OFF
3 = Standby
4 = Heat Request
5 = Config Error
0 - 5
42.
2. 1
BMS Level
%
42.
2. 2
BMS SetPoint
°C
42.
2. 3
BMS Input Voltage
V
42.
2. 4
BMS Input Current
mA