62
Operation
Parameter listing
24. 20 Other
24. 20. 0
DHW modulation setpoint
50 - 85
80
24. 20. 1
DHW program mode
0 = DHW time program
1 = Zone 1
2 = Zone 2
3 = Zone 3
4 = Zone 4
5 = Zone 5
6 = Zone 6
7 = Zones 1,2,3
8 = Zones 4,5,6
9 = All zones
10 = Disabled
0 - 10
0
24. 20. 2
Flue gas sensor type
0 = None
1 = NTC
2 = ON/OFF Thermostat
0-2
0
24. 20. 3
Flue gas supervision lockout
0 = Blocking
1 = Error
0-1
0
24. 20. 4
DHW tank discharge protection
ON/OFF
1-0
1
24. 20. 5
Boiler DHW recirculation pump
target (active with 3-way valve)
target temp
10 - 90°C
50
24. 20. 6
System DHW recirculation
pump target (active with LLH)
target temp
10 - 90°C
50
25 Cascade Management
25. 0 General
25. 0. 0
Max CH Adjustable Power perc
0 - 100%
100
25. 0. 1
Max DHW Adjustable Power perc
0 - 100%
100
25. 0. 2
Cascade Turnover Logic
0 = Minimum Switches Off-On
1 = Maximum Power Division
0 - 1
0
25. 0. 3
Turnover Hysteresis
0 - 20%
5
25. 0. 4
Min Turnover Level
0 - 100%
35
25. 0. 5
Max Turnover Level
0 - 100%
75
25. 0. 6
Maximum Water temp
20 - 95°C
90
25. 0. 7
CH differential temperature
0 - 20°C
0
25. 0. 8
CH/DHW shifting priority time
0 - 65535min.
0
25. 1 System Settings
25. 1. 0
Thermoregulation
0 = OFF
1 = ON
0 - 1
1
25. 1. 1
External temperature correction
-3 - 3°C
0
25. 1. 2
Boost Time
0 - 60min.
16
25. 1. 3
Plant frost protection
0 = OFF
1 = ON
0 - 1
0
Menu
Submenu
Parameter Name
Description
Range
Factory settings