57
Operation
Parameter listing
Menu
Submenu
Parameter Name
Description
Range
Factory settings
24. 5. 5
Boiler Tank charge mode
0 = Charge
1 = Full charge
2 = Full charge Legio
0 - 2
0
24. 5. 6
System Tank charge mode
0 = Charge
1 = Full charge
2 = Full charge Legio
0 - 2
0
24. 5. 7
Boiler DHW Circulating Pump
Release
0 = Release
1 = Time Program
2 = Special Time Program
0 - 2
0
24. 5. 8
System DHW Circulating Pump
Release
0 = Release
1 = Time Program
2 = Special Time Program
0 - 2
0
24. 5. 9
System DHW Charging Priority
0 = Absolute
1 = Shift
2 = None
0 - 2
0
24. 6
Configurable Inputs-Outputs
24. 6. 0
Multi In Temp 1
0 = None
1 = Common flow sensor
2 = DHW storage tank bottom
3 = DHW circulation sensor
4 = DHW charging sensor
5 = Buffer storage tank top
6 = Buffer storage tank bottom
7 = Flue gas temp sensor
0 - 7
1
24. 6. 1
Multi In Temp 2
0 = None
1 = Common flow sensor
2 = DHW storage tank bottom
3 = DHW circulation sensor
4 = DHW charging sensor
5 = Buffer storage tank top
6 = Buffer storage tank bottom
7 = Flue gas temp sensor
0 - 7
0
24. 6. 2
Multi In Temp 3
0 = None
1 = Common flow sensor
2 = DHW storage tank bottom
3 = DHW circulation sensor
4 = DHW charging sensor
5 = Buffer storage tank top
6 = Buffer storage tank bottom
7 = Flue gas temp sensor
0 - 7
0
24. 6. 4
PADIN 1 input
0 = None
1 = Room thermostat HC1 ON/OFF
2 = Room thermostat HC2 ON/OFF
3 = Room thermostat HC3 ON/FF
4 = 0- 10V input request (BMS)
5 = DHW time input
6 = Heat generator lock -applies for
complete cascade
7 = Gas Pressure Switch - applies for
complete cascade
8 = CH timer input
0 - 8
0