54
Operation
Parameter listing
Menu
Submenu
Parameter Name
Description
Range
Factory settings
4. 2. 2
Slope
LT: From 0.2 - 1.0
HT: From 0.4 - 3.5
0.6LT
1.3HT
Increase setting:
Increases the flow
temperature, especially at low
outside temperatures.
Reduce setting:
Reduces the flow temperature,
especially at low outside
temperatures.
flow temperature
outdoor temperature
room temperature
setpoint
°C
°C
low temperature level
high temperature level
23
23
21
21 19
19
30
20
10
0
40
50
60
70
80
90
°C
5
10
15
20
25
3.5 3.0
2.5
2.0 1.8
1.5
1.3
0.8
1.0
0.6
0.4
0
-5
-10
-15
-20
-25 °C
0.8
0.6
1.0
0.4
0.2
4. 2. 3
Offset
Offset heating line adjustable per °C
LT: From -7°C to +7°C
HT: From -14°C to +14°C
0
0
4. 2. 4
Room influence proportional
Only visible on the boiler if a room sensor
is connected
LT=2
HT=4
4. 2. 5
Max T
Zone 1 maximum Flow Temperature
LT: From 10°C to 45°C
HT: From 10°C to 90°C
LT 45
HT 85
4. 2. 6
Min T
Zone 1 minimum Flow Temperature
LT: From 10°C to 45°C
HT: From 10°C to 90°C
LT 20
HT 20
4. 2. 7
Thermo regulation logic
0 = Classic, 1 = Smart
0 - 1
0
4. 2. 8
Quick night setback
0 = OFF, 1 = ON
0 - 1
0
4. 2. 9
Heat request mode
0 = Standard
1 = RT Time Programs Exclusion
2 = Forcing Heat Demand
0 - 2
0
4. 3 Zone1 Diagnostics
4. 3. 0
Room T
°C
4. 3. 1
Room T setpoint
°C
4. 3. 2
Flow temperature
°C
4. 3. 3
Return temperature
°C
4. 3. 4
Heat request Z1
0 = OFF, 1 = ON
4. 3. 5
Pump status
0 = OFF, 1 = ON
4. 3. 9
Heating rate