65
Operation
Parameter listing
Menu
Submenu
Parameter Name
Description
Range
Factory settings
26..32. Commercial Boiler - Slave 1..
26..32. 0 General
26..32. 0. 0
Engines Number
26..32. 0. 2
Maximum Water temp
°C
90
26..32. 0. 3
Max CH Adjustable
%
100
26..32. 0. 4
Fan inc percentage
4
26..32. 0. 5
Altitude
m
0
26..32. 0. 6
Boiler tank solar integration
0
26..32. 0. 7
Emergency setpoint
°C
45
26..32. 0. 8
Max DHW adjustable
0-100 %
100
26..32. 3 Water Circulation
26..32. 3. 0
Max PWM Pump
46 - 95 %
95
26..32. 3. 1
Min PWM Pump
40 - 95%
46
26..32. 3. 2
CH pump overrun
0 - 16 min
5
26..32. 3. 3
Max pressure
2.0 - 6.0 bar
6
26..32. 5 Domestic Hot Water
26..32. 5. 0
DHW Setpoint Temperature
40 - 65°C
65
26..32. 5. 1
Comfort Function
0 = Disabled
1 = Time Based
2 = Always Active
0 - 2
0
26..32. 5. 3
Boiler DHW Mode
0 = CH Only
1 = DHW Tank NTC
2 = DHW Tank Thermostat
0 - 2
0
26..32. 5. 4
Anti-legionella Function
0 = OFF
1 = ON
0 - 1
0
26..32. 5. 5
Boiler DHW Charging Type
0 = Recharging
1 = Full charging
2 = Full charging Legio
0 - 2
0
26..32. 5. 7
Boiler DHW Circulating Pump Release
0 = Release
1 = Time Programs
2 = Circ Pump special Time Programs
0 - 2
0