55
Operation
Parameter listing
Menu
Submenu
Parameter Name
Description
Range
Factory settings
4. 7 Zone regulation parameters
4. 7. 0
Heating Type
0 = Floor Heating
1 = Radiatiors
2 = Floor Heating (main)+ radiators
3 = Radiators(main)+ Floor Heating
4 = Convection
5 = Air Heating
0 - 5
1
4. 7. 1
Room Influence
0 = Off
1 = Less
2 = Medium
3 = More
0-3
0
4. 7. 2
Building Isolation Level
0 = Poor
1 = Averige
2 = Good
0-2
0
4. 7. 3
Building Size
0 = Small
1 = Average
2 = Large
0 - 2
0
4. 7. 4
Climatic Zone
+50 to -60 °C
-10
4. 7. 5
Auto Slope Adaptation
0 = OFF
1 = ON
0 - 1
0
4. 7. 6
Pre-Heating Function
0 = OFF
1 = ON
0 - 1
0
5
Zone2 Parameters (see Zone1, chapter 4)
6
Zone3 Parameters (see Zone1, chapter 4)
20
Buffer
20. 0
Configuration
20. 0. 0
Buffer Activation
0 = OFF
1 = ON
0 - 1
0
20. 0. 1
Buffer charge mode
0 = Not defined
1 = Partial charge
2 = Full charge
0 - 1
1
20. 0. 2
Buffer setpoint temperature hysteresis
0 - 20 °C
5°C
20. 0. 3
Buffer heating Comfort setpoint temperature
20 - 70°C
40°C
20. 0. 4
Buffer cooling Comfort setpoint temperature
5 - 23°C
18°C
20. 0. 7
Buffer setpoint mode
0 = Fixed
1 = Variable
0 - 1
0 - 1
20. 0. 8.
Buffer hysteresis cooling
°C
[0; 20]
20. 1 Diagnostics
20. 1. 0
Low sensor temperature
°C
20. 1. 2
High sensor temperature
°C
20. 4 System settings
20. 4. 0
Buffer Integration Scheme
0 = Series
1 = Parallel
0 - 1
20. 4. 1
Buffer Solar Integration
0 = No
1 = Yes
0 - 1