80
Commissioning
Weather compensation
Select thermoregulation type
To set the boiler to weather compensation, please set parameter 4.2.1 to 3 with an ON/OFF or eBus controller.
1 Use
“+”
to go down and
“–”
to go
up to highlight the Parameters Zone
you want to set. In this case
Zone 1 Parameters
.
Press
OK
.
2
Use
“+”
to go down and
“–”
to go
up to highlight
4.2 Z1 Settings
.
Press
OK
.
3
Use
“+”
to go down and
“–”
to go
up to highlight
4.2.1 Thermoregulation
.
Press
OK
.
4 Make a choise between
5
:
0 Fix Flow T
Room thermostat with fixed flow temperature
(Tstart 58°C)
1
, every 16 min ±4 K)
1)
= Factory setting at high temperature level
1 Basic Thermoreg
Room thermostat with automatic flow temperature adaptation
2 Room T Only
Pure room temperature control with room sensor
The flow temperature is controlled as a function of the room temperature
setpoint, the current room temperature and its current course. A slight
increase in the room temperature, for example, immediately reduces the
flow temperature.
3 Outdoor T Only
Weather dependent control with outdoor sensor
The flow temperature is calculated via the heating curve as a function of the
current outdoor temperature. This type of control requires that the heating
characteristic is set correctly, as the control system does not take room
temperature into account in this setting.
4 Room + Outdoor T
Weather and room temperature control with outdoor and room sensor
The deviation of the room temperature from the setpoint is recorded and
taken into account during temperature control. In this way, any external heat
generated can be taken into account and a more constant room temperature
becomes possible.
The influence of the deviation is set proportionally. The better the reference
room is (unaltered room temperature, correct installation location, etc.), the
higher the value can be set.
Example:
Approx. 4: Good reference room
Approx. 1: Unfavourable reference room
0 Network
4
Zone1 Parameters
5
Zone2 Parameters
6
Zone3 Parameters
24
Commercial boiler
Menu
0 Network
4.1
S/W Changeover
4.2 Settings
4.0 Setpoint
4.3 Diagnostics
4 Zone1 Parameters
4.2.1 Thermoregulation
0
4.2.2 Slope
1.5
4.2.4 Room Influence Proportional
10
4.2.0 Zone temperature range
1
4.2.3 Offset
0
4.2 Settings