67
Operation
Parameter listing
Menu
Submenu
Parameter Name
Description
Range
Factory settings
26..32. 6. 6
PADIN 3 input
0 = None
1 = Room thermostat HC1 ON/OFF
2 = Room thermostat HC2 ON/OFF
3 = Room thermostat HC3 ON/FF
4 = 0- 10V input request (BMS)
5 = DHW time input
6 = Heat generator lock only applies on the boiler
(not complete cascade)
7 = Gas Pressure Switch - only applies on the
boiler (not complete cascade)
8 = CH timer input
0 - 8
0
26..32. 6. 7
PADIN 4 input
Gas Pressure Switch - only applies on the boiler
(not complete cascade)
7 - 7
7
26..32. 7.
Configurable Input- Output 2
26..32. 7. 0
MO1 output HV
230Vac
0 = None
1 = System pump (25.1.6)
2 = HC1 Pump
3 = DHW re-circulating pump
4 = DHW charging pump
5 = BUF filling pump
6 = Storage tank transfer pump
0-6
0
26..32. 7. 1
VFR 1 output 1
0 = None
1 = System pump (25.1.6)
2 = HC1 Pump
3 = DHW re-circulating pump
4 = DHW charging pump
5 = BUF filling pump
6 = Storage tank transfer pump
7 = Heat generation shut off valve
8 = Heat request
9 = Alarm output
10 = LPG/ Room Supply Fan
0-10
0
26..32. 7. 2
VFR 2
0 = None
1 = Heat generation shut off valve
2 = Heat request
3 = Alarm output
4 = LPG/ Room Supply Fan
0-4
0
26..32. 7. 3
VFR 3
0 = None
1 = Heat generation shut off valve
2 = Heat request
3 = Alarm output
4 = LPG/ Room Supply Fan
0-4
0
26..32. 7. 4
MO1 output PWM or
0-10V for BMS
0-10 Volt feedback active only inverted
5-5
5
26..32. 7. 5
MO2 output PWM or
0-10V for BMS
0-10 Volt feedback active only inverted
5-5
5
26..32. 8 Boiler manual settings
26..32. 8. 0
Manual mode activation
0 = OFF
1 = ON
0 - 1
0