58
Operation
Parameter listing
24. 6. 5
PADIN 2 input
0 = None
1 = Room thermostat HC1 ON/OFF
2 = Room thermostat HC2 ON/OFF
3 = Room thermostat HC3 ON/FF
4 = 0- 10V input request (BMS)
5 = DHW time input
6 = Heat generator lock only applies on
the boiler (not complete cascade)
7 = Gas Pressure Switch - only applies on
the boiler (not complete cascade)
8 = CH timer input
0 - 8
0
24. 6. 6
PADIN 3 input
0 = None
1 = Room thermostat HC1 ON/OFF
2 = Room thermostat HC2 ON/OFF
3 = Room thermostat HC3 ON/FF
4 = 0- 10V input request (BMS)
5 = DHW time input
6 = Heat generator lock only applies on
the boiler (not complete cascade)
7 = Gas Pressure Switch - only applies on
the boiler (not complete cascade)
8 = CH timer input
0 - 8
0
24. 6. 7
PADIN 4 input
Gas Pressure Switch - only applies on the
boiler (not complete cascade)
7 - 7
7
24. 7
Configurable Inputs-Outputs 2
24. 7. 0
Multi Out HV
0 = None
1 = System pump
2 = HC1 Pump
3 = Circulating pump
4 = DHW intermediate circuit pump
5 = BUF filling pump
6 = Storage tank transfer pump
7 = Heat generation shut off valve
8 = None
0 - 8
1
24. 7. 1
VFR 1 output 1
0 = None
1 = System pump (25.1.6)
2 = HC1 Pump
3 = Circulating pump
4 = DHW charging pump (only active with
3-way valve)
5 = BUF filling pump
6 = Storage tank transfer pump
7 = Heat generation shutoff valve
8 = Heat request
9 = Alarm output
10 = LPG/ Room Supply Fan
0 - 10
0
24. 7. 2
VFR 2
0 = None
1 = Heat generation shut off valve
2 = Heat request
3 = Alarm output
4 = LPG/ Room Supply Fan
0 - 4
0
Menu
Submenu
Parameter Name
Description
Range
Factory settings