56
Operation
Parameter listing
Menu
Submenu
Parameter Name
Description
Range
Factory settings
24 Commercial Boiler
24. 0 General
24. 0. 2
Maximum Water temp
20 - 95 °C
90
24. 0. 3
Max CH Adjustable
0 - 100 %
100
24. 0. 4
Fan increment percentage
4 - 100 %
4
24. 0. 5
Altitude
0 - 1000 m
0
24. 0. 6
Boiler tank solar integration
0 = Absent
1 = Present
0 - 1
0
24. 0. 7
Emergency setpoint
20 - 90 °C
45
24. 0. 8
Max DHW adjustable
0-100 %
100
24. 3. Water Circulation
24. 3. 0
Max PWM Pump
46 - 95 %
95
24. 3. 1
Min PWM Pump
40 - 95 %
46
24. 3. 2
CH pump overrun
0 - 16 min.
5
24. 3. 3
Max pressure
2.0 - 6.0 bar
6.0
24. 4. System Setting
24. 4. 0
Thermoregulation
0 = OFF
1 = ON
0 - 1
1
24. 4. 1
External temperature
correction
-3 to +3°C
0
24. 4. 2
Boost Time
0 - 60 min
16
24. 4. 3
Plant frost protection
0 = OFF
1 = ON
0 - 1
0
24. 4. 4
T Gradient
0 - 15°C
5
24. 4. 5
System Pump Overrun
0 - 255 min
5
24. 4. 6
System pump activation logic
0 = Always active
1 = Heating only
0 - 1
0
24. 4. 7
System tank solar integration
0 = Absent
1 = Present
0 - 1
0
24. 4. 8
CH/DHW shifting priority time
0 - 65535
0
24. 4. 9
HC pump overrun DHW
0 - 1
0
24. 5 Domestic Hot Water
24. 5. 0
DHW Setpoint Temperature
20 - 80 °C
60
24. 5. 1
Comfort Function
0 = Disabled
1 = Time Based
2 = Always Active
0 - 2
2
24. 5. 2
System DHW Mode
0 = CH Only
1 = Storage with NTC
2 = Storage with Thermostat
0 - 2
0
24. 5. 3
Boiler DHW Mode
0 = CH Only
1 = Storage with NTC
2 = Storage with Thermostat
0 - 2
0
24. 5. 4
Thermal cleanse function
0 = OFF
1 = ON
0 - 1
1