User Manual
114
KDC Series II DC Power Supplies
28V system:
1. 22V for 1 minute.
2. 29V for 1 minute.
3. 28V for 1 minute.
270V system:
1. 250V for 1 minute.
2. 280V for 1 minute.
3. 270V for 1 minute.
The
key (backspace) will terminate the test at any time.
RIPPLE
This test will impose a 400Hz frequency component to the output voltage. The test will last for 2
minutes. The level of the ripple is as follows:
28V system:
1.5V.
270V system:
6.0V.
The
key (backspace) will terminate the test at any time.
11.2.9 Transient Test
From the MIL704 DC MENU scroll to the TRANSIENT MENU entry using the up and down
cursor keys. Press the ENTER key to select the TRANSIENT TEST screen. The screen will
appear as shown in.
Figure 11-9: Transient Menu
The Transient Test has the following tests:
1
HIGH VOLTAGE
2
LOW VOLTAGE
HIGH VOLTAGE
This test will change the output voltage for the selected phase in the following sequence:
28V System
1. 50V for 12.5 msec.
2. Linearly reduce to29V in 70msec.
3. Stay at 29V for 92.5msec before returning to 28V.
270V System
330V for 20 msec.
Содержание KDC 100-100
Страница 2: ......
Страница 10: ......
Страница 26: ...User Manual 16 KDC Series II DC Power Supplies Figure 3 1 Location of rear panel connectors ...
Страница 33: ...User Manual KDC Series II DC Power Supplies 23 Figure 4 3 Front panel layout ...
Страница 82: ......
Страница 83: ...User Manual KDC Series II DC Power Supplies 73 Figure 6 1 DC Power Supply Block Diagram ...
Страница 84: ...User Manual 74 KDC Series II DC Power Supplies Figure 6 2 DC Power Supply Block Diagram with IF option ...
Страница 111: ...User Manual KDC Series II DC Power Supplies 101 Figure 8 2 Replaceable Fuse Locations ...