User Manual
KDC Series II DC Power Supplies
63
5.2.1.1 Configuring the auxiliary units.
Parallel operation requires the use of a suitable interconnect cable between the Master power
source J22 15 pin connector and each Auxiliary power J22 15 pin connector. Connectors for this
purpose are supplied in the ship kit of each KDC unit.
The interconnect cable must be wired such that J22 pin 7 of the Master unit connects to J22 pin
11 of each Auxiliary unit. J22 pin 14 of the Master source must connect to J22 pin 14 of each
Auxiliary source. Note that this cable must be marked “MASTER” and “AUX” as the correct
orientation of connection is important.
A suitable interconnect cable for a two unit parallel system can be order through AMETEK
Programmable Power customer service department (
). Specify
AMETEK P/N 5005-053-1.
Figure 5-7: Parallel Cable Interconnect Accessory
5.2.1.2 Auxiliary unit controller configuration
The auxiliary KDC units‟ controllers must be configured for auxiliary mode. Units with the –AUX
option on the model serial tag have been configured as an auxiliary unit at the factory. If the unit
was not factory configured, it has to be reconfigured. This requires the top cover to be removed.
With the top cover removed, check the position of jumpers W17 and W18 on the Controller CPU/
Analog board, assembly P/N 5005-721. For operation as an Auxiliary power source, remove
jumper W17 and install jumper W18. Refer to Table 5-1.
Reinstall the top cover once all jumper settings are correct.
Содержание KDC 100-100
Страница 2: ......
Страница 10: ......
Страница 26: ...User Manual 16 KDC Series II DC Power Supplies Figure 3 1 Location of rear panel connectors ...
Страница 33: ...User Manual KDC Series II DC Power Supplies 23 Figure 4 3 Front panel layout ...
Страница 82: ......
Страница 83: ...User Manual KDC Series II DC Power Supplies 73 Figure 6 1 DC Power Supply Block Diagram ...
Страница 84: ...User Manual 74 KDC Series II DC Power Supplies Figure 6 2 DC Power Supply Block Diagram with IF option ...
Страница 111: ...User Manual KDC Series II DC Power Supplies 101 Figure 8 2 Replaceable Fuse Locations ...