User Manual
KDC Series II DC Power Supplies
3
2 Specifications
All specifications at 23 5 C unless noted otherwise.
2.1 Electrical
2.1.1
Input Voltage
Standard:
-208:
208 VAC L-L -10% to 230VAC L-L +10 %
Options:
-400:
400VAC L-L ± 10 %
-480:
480VAC L-L ± 10 %)
Frequency:
50 to 60 Hz ± 3 Hz
Phases:
3-phase, 3-wire plus safety ground
Power Factor:
> 0.65 typical.
2.1.2
Maximum Input Current per Phase at Low Line
Current
5 KW
10 KW
15 KW
Standard
-208
27A
54A
81A
Options
-400
-480:
18A
18A
36A
36A
54A
54A
Recommended circuit protection per phase. (CB)
Standard
-208
30A
60A
90A
Options
-400
-480:
20A
20A
40A
40A
60A
60A
2.1.3
Output Power
DC Power:
See section 2.1.5. Maximum power is available at full-scale
voltage.
2.1.4
Output Voltage
Voltage
Voltage Ranges:
See section 2.1.5
Voltage Programming:
Internal
Accuracy: 0.05 % S 0.1 % FS
Resolution: 0.025 % FS
Analog Input
Accuracy: 0.1 % S 0.2 % FS
Noise and Ripple:
See section 2.1.5
Line Regulation:
< 0.1% of V Range
Load Regulation:
< 0.1% of V Range
Содержание KDC 100-100
Страница 2: ......
Страница 10: ......
Страница 26: ...User Manual 16 KDC Series II DC Power Supplies Figure 3 1 Location of rear panel connectors ...
Страница 33: ...User Manual KDC Series II DC Power Supplies 23 Figure 4 3 Front panel layout ...
Страница 82: ......
Страница 83: ...User Manual KDC Series II DC Power Supplies 73 Figure 6 1 DC Power Supply Block Diagram ...
Страница 84: ...User Manual 74 KDC Series II DC Power Supplies Figure 6 2 DC Power Supply Block Diagram with IF option ...
Страница 111: ...User Manual KDC Series II DC Power Supplies 101 Figure 8 2 Replaceable Fuse Locations ...