Result:
•
The cable is prepared.
6.3.8
Establishing electrical connections on the VECTOPOWER VP5000-
DC/DC60
Information:
All electrical connections are located on one side of the VECTOPOWER. They are labeled on the
housing.
Figure 84: Position of the electrical connections on the VECTOPOWER VP5000-DC/DC60
Overview of the tightening torques of the screws for the housing cover:
Cable gland
Tightening torque
Screws for the housing cover
1.0 Nm / 8.9 inlb
Table 44: Tightening torques of the housing cover screw fitting
Overview of the tightening torques of the screws for the cable lugs:
Cable gland
Tightening torque
Screws for cable lug for the [DC+/-], [/-], and
ground wire connections
15.0 Nm / 132.8 inlb
Table 45: Tightening torques of cable lug screw fittings