VP5000-DC/DC60, VP5000-DC/DC200-HL
Product description
Last edited 2019-02-08
by Sonja Scheunert
Filename
VP5000_DCDC60_200-HL_installation_manual_v1-4en.docx
26 / 173
VECTOPOWER
VP5000-DC/DC60
VECTOPOWER
VP5000-DC/DC200-HL
Recommended DC link
rated voltage [DC+/-]
650 V DC
Maximum DC link voltage
[DC+/-]
770 V DC
Switch-off threshold 1 DC
link voltage [DC+/-]
Hardware version 1.0 720 V DC triggering level
Hardware version 1.1 and higher: 800 V DC triggering level
Switch-off threshold 2 DC
link voltage [DC+/-]
820 V DC
Minimum output voltage
[/-]
Rule: 10% of the actual DC link
voltage [DC+/-], but at least 20 V DC
[DC+/-] 48 V DC to 199 V DC ->
minus 20 V DC
Example: [DC+/-] 48 V DC -
20 V DC= [/-] 28 V DC
[DC+/-] 200 V DC to 800 V DC ->
10%
Example [DC+/-] 220 V DC, of which
10% = [/-] 22 V DC
20 V DC
Maximum output voltage
[/-]
Rule: Maximum 90% of the actual DC
link voltage [DC+/-], but at least
20 V DC lower than the actual DC link
voltage [DC+/-] and not more than
750 V DC maximum
[DC+/-] 48 V DC to 199 V DC ->
minus 20 V DC
Example: DC link [DC+/-] 50 V DC -
20 V DC = [/-] 30 V DC
[DC+/-] 200 V DC to 800 V DC ->
90%
Example: DC link [DC+/-] 650 V DC,
of which 90% = [/-]
585 V DC
Rule: Actual DC link voltage [DC+/-]
minus 20 V DC
Example: [DC+/-] 650 V DC -
20 V DC = [/-] 630 V DC
Max. positive / negative
continuous current on the
output side [/-]
110 A DC at 650 V DC in the DC link
[DC+/-], 30 l/min / 8 gpm coolant at
35 °C / 95 °F and 45 °C / 113 °F
ambient temperature
400 A DC at 650 V DC in the DC link
[DC+/-], 30 l/min / 8 gpm coolant at
35 °C / 95 °F and 45 °C / 113 °F
ambient temperature
Max. positive / negative
continuous current with
derating on the output side
[/-]
90 A DC at 650 V DC in the DC link
[DC+/-], 30 l/min / 8 gpm coolant at
65 °C / 95 °F and 45 °C / 149 °F
ambient temperature
350 A DC at 650 V DC in the DC link
[DC+/-], 30 l/min / 8 gpm coolant at
65 °C / 95 °F and 45 °C / 149 °F
ambient temperature