VP5000-DC/DC60, VP5000-DC/DC200-HL
Installation and commissioning
Last edited 2019-02-08
by Sonja Scheunert
Filename
VP5000_DCDC60_200-HL_installation_manual_v1-4en.docx
125 / 173
Figure 92: Covers on the VECTOPOWER VP5000-
DC/DC60
Close the housing:
16.
Put on the other cover (1).
17.
Tighten the screws for the cover (1)
according to the following procedure:
In the first step, tighten the screws
crosswise with a tightening torque of
<
1
Nm / <
8.9
inlb.
In the second step, tighten the screws
crosswise with a tightening torque of
1 Nm / 8.9 inlb.
18.
Put on the other cover (2).
19.
Tighten the screws for the cover (2)
according to the same procedure and with
the same tightening torques as for the first
cover (1).
Figure 93: Logical connections on the
VECTOPOWER VP5000-DC/DC60
Connect the logical connections:
•
The connections are labeled on the
housing.
20.
[ST1] engages during insertion.
(To release the connector [ST1], press
down on the nose with a screwdriver.)
21.
Establish EMC compatibility for [ST1] with
a shield bus, shield clamp, shield terminal,
or similar. You can connect the shielding
to one of the two ground wires on the
VECTOPOWER housing.
22.
[ST2], [ST3], and [ST4] are screwed
together.