22
-
English
CONTROL NK
CONTROL UNIT
START-UP
5.
When you have completed and checked the electri-
cal connections, before powering the system, make the
DIPSWITCH SETTINGS for
DP1
DIPSWITCH group as
described below.
Settings (DP1 DIP-SWITCH group)
5.1
Tab. 6
illustrates the possible settings using the
DP1
DIPSWITCH group.
1
Partial opening - when traffi c is considerable, it is
established if the partial opening remains as set using the
trimmer P6 or is adapted (it increases automatically as the
traffi c increases and vice versa).
2
Break-in - if there is a break-in attempt, it is established
if the automation is free (the gear motor is not triggered) or
resistant (the motor prevents wing opening).
3
M/S
-
Master/Slave mode is enabled or disabled when
two automations are connected to each other.
4
Closing speed - adjusts the closing speed value as a
percentage of the opening speed (also see Trimmer
P5
).
5 Photocell - to set the type of contact used for the obstacle
detection photocells: NO or NC.
6 Continuation during power failure - if the mains power
fails, continuation of the mode set is enabled or disabled
(using the emergency batteries). If continuation is disabled,
when there is a power failure, the operation set using DIP7
is carried out immediately.
7 Last operation during power failure - if the mains power
fails, this establishes the operation for the automation to
perform using the emergency batteries: opening or closing.
The door stops in this position until the power returns.
Note: Dipswitches 6 and 7 are connected: if continuation is
enabled, the last operation is only carried out when the batteries
reach the critical voltage threshold; if not, the last operation is
carried out when the power fails.
Note: when the power returns, the automation starts to operate
again in the mode set previously.
8 Exit only electric lock - enables or disables the lock for
every closing operation when the automation is in automatic
EXIT ONLY mode.
9 Emergency - establishes the operation which the
automation performs if the emergency button is pressed:
opening or closing (the door stops in this position).
Note: when the PE emergency pushbutton is released, the
automation starts to operate again in the mode set previously.
10 N.L. mode power failure - establishes electric lock
maintained or OFF if there is a power failure when the door
is set to Night Lock mode.
11 N.L. mode stop - enables or disables the Stop with
mechanical emergency when the door is set to Night Lock mode.
12 not used.
Settings by DP1 DIP-SWITCH group
tab. 4 -
DP1 DIP-SWITCH
tab. 5 -
group factory settings
LED functions
tab. 6 -
Trimm
fig. 8 -
er and LED
DP1
Dip-Switch group Position
0 (OFF)
Position
1 (ON)
1 Partial opening fi xed
adaptative
2 Break-in
free
resists
3 Master-Slave
M/S enabled
M/S disabled
4 Closing speed
75% opening
speed
equal to opening
speed
*
5 Photocell
N.O.
N.C.
6 C o n t i n u a t i o n
during power
failure
enabled
disabled
7 Last operation
during power
failure
closes
opens
8 E l e c t r i c l o c k
only for Exit
disabled
enabled for every
closure
9 Emergency
closes
opens
10 power failure in
N.L. mode
releases the door maintains locked
11 STOP input in
N.L. mode
STOP disabled
STOP enabled
12 not active
* self-learned/set with trimmer P5
DL1
Diagnostic and alarms
DL2
(verde)
Mains power supply presence
DL9
(visibile lato connettore
J9
) Lock inserted
Accessory devices connected to terminal board
K3
(see Fig.7)
:
EMR
EMERGENCY pushbutton
RAD.1
Entrance RADAR
RAD.2
Exit RADAR
FOTO
Photocell
STOP
STOP pushbutton
M/S
Master/Slave mode
BUZZER
RESET
SW1
P1
P2
P3
P4
P5
P6
RIT. BN
ON
1 2 3 4 5 6 7 8 9 10 11 12
V. AVV.
F. SPI.
T. SOS.
VELOC.
% AP. P.
RADAR
SW2
DL2
DP1
JP1
ISP
JP3
MERGENCY
RADAR 1
TEST PHOTOC.
RADAR 2
HOTOCELL
STOP
M/S COM
M/S OUT
M/S IN
18
17
16
15
14
13
12
11
10
J7
KEY
SELECTOR
J13
DO
NOT
TOUCH
DO
NOT
TOUCH
Trimmer
DIP SWITCH
EMR
RAD.1
RAD.2
FOTO
STOP
M/S
DL9
ON
OFF
1
Ö
OFF
(fi xed partial opening)
2
Ö
OFF
(door free after break-in attempt)
3
Ö
ON
(M/S disabled ; 1st input enabled)
4
Ö
ON
(closing speed = 100% of opening speed)
5
Ö
ON
(photocell contact = N.C.)
6
Ö
OFF
(continuation during power failure)
7
Ö
ON
(last operation = door opening)
8
Ö
OFF
(electric lock disabled in exit only mode)
9
Ö
ON
(emergency operation = door opening)
10
Ö
OFF
(NO door release during power failure)
11
Ö
ON
(disables STOP in Night lock mode)
12
Ö
OFF
(not active)