Page 31
TITANUS
PRO·SENS
®
TECHNICAL MANUAL
TITANUS
PRO·SENS
®
-SL
TITANUS
PRO·SENS
®
2
-SL
Voltage
supply voltage (Ue)
nominal supply voltage
14 to 30 V DC
24 V DC
Strom
Voltage with
ventilator control board FC-2
U
L
9
=
6,5 V
U
L
=
6,9 V
U
L
=
9 V
U
L
=
6,5 V
U
L
=
6,9 V
U
L
=
9 V
starting current (at 24V)
(without additional module)
300 mA
330 mA
quiescent current consumption
(at 24 V)
(without additional module)
140
mA
150
mA
180
mA
170
mA
180
mA
210
mA
current consumption alarm
(at 24V)
(without additional module)
max.
150
mA
max.
160
mA
max.
190
mA
max.
180
mA
max.
190
mA
max.
220
mA
Voltage with
ventilator control board FC-3
10
U
L
=
10 V
U
L
=
11V
U
L
=
12V
U
L
=
10 V
U
L
=
11 V
U
L
=
12 V
starting current (at 24V)
(without additional module)
300 mA
330 mA
quiescent current consumption
(at 24 V)
(without additional module)
180
mA
200
mA
230
mA
230
mA
240
mA
270
mA
current consumption alarm
(at 24V)
(without additional module)
max.
200
mA
max.
210
mA
max.
240
mA
max.
260
mA
max.
260
mA
max.
290
mA
current consumption reset board
max. 20 mA
current consumption network
module
max. 40 mA
current consumption shutdown
module
max. 6 mA
contact load of alarm and fault
relays
switching power
30 V, 1 A
max. 24 W
Dimensions
dimensions (h x b x d mm)
113 x 200 x 292 mm
Weight
weight
1.35 kg
Noise level
L
wa
according to EN ISO 3744,
1995 (without noise suppressor)
at 31 dB(A)
according to ventilator voltage
L
wa
according to EN ISO 3744,
1995 (with noise suppressor)
at 23 dB(A)
according to ventilator voltage
9
U
V
= ventilator voltage
10
FC-3 =optional available