Page 130
TITANUS
PRO·SENS
®
TECHNICAL MANUAL
8.6
Changing the air filter LF-AD -x
Fig. 8.2: change the filter inserts
To change the filter inserts, carry out the following steps (see fig. 8.2):
1
Loosen the four screws and remove the housing lid.
2
Remove the filter inserts and check how soiled they are. The inserts
can be cleaned if there is a small amount of soiling and must be
replaced if soiling is heavy
3
Carefully clean the inside of the housing from dust deposits. Now
replace the cleaned or new filter inserts in the correct sequence.
This can be seen on the sign on the housing floor.
4
Replace the housing lid and screw it shut.
In environments with a high level of fine-grade dust, three optional fine dust
filters can be used in addition.
Opening the housing lid of the air filter LF-AD causes an air flow fault in
TITANUS
PRO·SENS
®
.
TIP
INSTRUCTION