6.8
3-Way ball valve
Fig. 6.11: Installation of 3-way ball valve
The ball valve is required for blowing-through with compressed air
33
(preferably).
The ball valve switches between fire detection (position 0°) and blowing-through
(position 180°). Connect the ball valve to the pipe system by means of the
screw joints.
Connections
During installation pay attention to the correct connectors (refer to scheme in
Fig. 6.11):
Connect the pipe system to connector C.
Mount TITANUS
®
to the connector A or B and the compressed air supply to
the remaining connector.
33
Depending on the temperature use either compressed, non-purified and humid ambient air or
purified and dehumidified air. If the air sampling system and the pipe system are located in areas below the
freezing point purified and dehumidified compressed air should be used.