Fig. 4.22: Air recirculation
Air recirculation
The air recirculation must take place at a distance of at least 2 m from the
sampling. The open end of the air recirculation should be bevelled at a 45°
angle (see Fig. 4.22).
Fig. 4.23 Offset air recirculation reengagement
If a distance of 2 m cannot be maintained, the pipes will have to be arranged in
an offset manner. This make makes it possible to achieve a drop of pressure
between the intake airs and exhaust air, since the pipes are located in different
flow rate areas.