Page 93
TITANUS
PRO·SENS
®
TECHNICAL MANUAL
5.7
Installation of the second detector module
Fig 5.14: Installation of the second detector module
1
Only
carry out the following work if the device is current-free.
2
With a slot screwdriver, carefully undo the snap-in closures of the
housing by simultaneously pressing in the clips located on one
side. Then carefully lift the housing lid. Pull the cable from the
display board and remove the lid.
3
Carefully remove the cover from the second air sampling pipe
(plastic self-adhesive cover). If necessary use a screwdriver to
assist.
4
Carefully break the closure connecting the second pipe system
and the housing (correct breaking point marked by “II”), again
using a screwdriver if required.
5
Spread both support clamps and place the new detector module
between them
.
Both clamps must fit tightly against the module
and snap in audibly. Press both support clamps together.
6
Pull (remove) the jumper JU4 from the base board (see fig. 5.22).
7
Connect the detector module to the base board via the ribbon
cable. Connection: X3 HEAD 2 (see fig. 5.22)