Page 102
TITANUS
PRO·SENS
®
TECHNICAL MANUAL
6.2
Patented air sampling points
Fig. 6.2: Example of an air sampling hole with an aspiration-reducing film sheet
Air Sampling Points
The layout of the air sampling points (air sampling hole) is to be designed
according to the requirements of the project and the guidelines of the pipe
design.
Air Sampling Holes
1.
Place a 10 mm-air sampling hole in a right angle towards the pipe.
2. Clean and trim the holes carefully.
3. Clean the area of the hole (throughout the whole pipe) from dirt and grease
by means of an agent, e.g. Tangit cleaning agent.
4. Select the size of the aspiration-reducing film sheet according to the
recommendations of the
pipe design
.
5. Place the aspiration-reducing film sheet on the hole (refer to Fig. 6.3
).
6. Prevent the film sheet from falling off by sticking marking tape on the film
sheet (refer to Fig. 6.3
).
The perforations in the aspiration-reducing film sheet and the marking tape
are to be placed exactly on the hole in the pipe. The diameter of the
perforation in the aspiration-reducing film sheet must not be changed.
Avoid touching the adhesive in order to keep it free from dust and oil.
INSTRUCTION