![Ampac TITANUS PRO SENS Скачать руководство пользователя страница 138](http://html.mh-extra.com/html/ampac/titanus-pro-sens/titanus-pro-sens_technical-manual_2934130138.webp)
Page 134
TITANUS
PRO·SENS
®
TECHNICAL MANUAL
8.9
Check air flow monitoring
A pipe fracture or pipe blockage shows for each detector module via a flash
code LED on the base board. Proceed according to chapter 7.3 "Air Flow
Monitoring".
8.10 Check fault signal transmission
A fault is shown on TITANUNS PRO
·SENS
®
and if necessary on the central fire
panel.
Proceed according to chapter 7.4 “Fault Signal Transmission”.
8.11 Maintenance intervals
Maintenance includes regular inspection. The air sampling smoke detection
systems are checked during commissioning and then every three months
(quarterly). Every fourth inspection includes additional checks which lead to the
following distinction:
quarterly check
inspection
annual check
maint 4
th
annual inspection
Type of Check
Measure
Further Information
in Chapter
inspection
visual check
check detector module and
alarm transmission
check pipe system
check air flow sensor
adjustment
check fault signal transmission
8.1
8.3
8.4
8.8
7.4
maint
4th annual
inspection
visual check
check detector module and
alarm transmission
check pipe system
check air flow sensor
adjustment
check fault signal transmission
check air flow monitoring
8.1
8.3
8.4
8.8
7.4
7.3