![Ampac TITANUS PRO SENS Скачать руководство пользователя страница 102](http://html.mh-extra.com/html/ampac/titanus-pro-sens/titanus-pro-sens_technical-manual_2934130102.webp)
Page 98
TITANUS
PRO·SENS
®
TECHNICAL MANUAL
Installation instructions
The pipe system must be designed according to the
requirements of the project and the pipe design guidelines
(see chapter 4 "Pipe Design").
1. Cut the pipes with a pipe cutter or a metal saw. Chips must be removed and
rough edges trimmed.
2.
Before
gluing, remove any dirt and grease from the joints with the
recommended cleaning agent. Glue the pipe ends to the corresponding
fittings so that they are airtight
Air Sampling
Pipe, halogen-
free
Air
Sampling
Pipe (PVC)
Cleaning
Agent
Adhesive
Pipe Cutter
ABSR-2518,
ABSR-3220,
ABSR-4025
R-2519,
R-3218,
R-4019
Tangit
cleaner
Tangit
adhesive
pipe cutter or
38mm saw
Adhesives and cleaning products contain solvents and are flammable. It is
essential to observe the supplier’s safety information before processing.
3.Keep the pipe lengths and direction changes to a minimum. Elbows and
bends have an extremely high flow resistance. Use them only where this is
unavoidable. Should this be necessary, the pipe length must then be
reduced in relation to the fitted bends
32
.
Arcs should be used instead of elbows. If the number of changes of
direction is too high an air flow fault can occur at TITANUS
PRO·SENS
®
and the detection time can be changed..
4. The pipes must be installed in such a way that they do not sag or move.
They are fixed with pipe clips
without
rubber core. The space between the
pipe clips should be no more than 80cm. Reduce the space between clips to
no more than 30cm if there are high temperature variations.
32
An arc equals a straight piece of pipe of 0.3 m
an elbow equals a straight piece of pipe of 1.5m
ATTENTION
INSTRUCTION