Page 76
TITANUS
PRO·SENS
®
TECHNICAL MANUAL
5.3.1.2 Delay period of the alarm activation
The delay period for the alarm thresholds can be set via the switch S1 (3, 4). As
a standard the delay period for the alarm is set to 10 sec. If the smoke level
increases during operation so that the alarm threshold is reached the delay
period starts. After the delay period has been expired the signal is transmitted if
the alarm remains activated. Thus, a false alarm can be avoided in case of
short interferences (dust).
Alarm
Delay Period
Switch S1
Contact 3
Switch S1
Contact 4
0 seconds
off
off
10 seconds (standard)
on
off
30 seconds
off
on
60 seconds
on
on
The alarm delay period should be set to 0 seconds for test purposes only.
5.3.1.3 Activating threshold of the air flow monitoring
Set the activating threshold of the air flow fault via the switch S1 (5, 6) on the
detector module (see fig. 5.2) of TITANUS
PRO·SENS
®
.
Level
Activating Threshold
Switch S1
Contact 5
Switch S1
Contact 6
I
small
on
off
II
medium (standard)
off
on
III
large
off
off
IV
very large
on
on
Choose the activating threshold according to chapter 4, "Pipe Design".