Page 154
TITANUS
PRO·SENS
®
TECHNICAL MANUAL
Projection with air filter SF-400 / SF-650
M = Module
S = Sensitivity (% Lt/m)
HA = Fire alarm
VA = Action alarm
Number of points
M
S
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
18
20
21
22
24
32
0.015
0.015
HA
A
A
A
A
A
B
B
B
B
B
B
B
C
C
C
C
C
C
C
C
C
0.03
HA
A
A
B
B
B
B
C
C
C
C
C
C
0.06
HA
A
B
B
C
C
C
0.12
HA
B
C
C
0.1
0.1
HA
A
B
C
C
C
0.2
HA
B
C
0.4
HA
C
0.8
HA
0.5
0.5
HA
C
1
HA
without additional pipe accessories
Pipe
shape
U
Fan
[V]
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
18
20
21
22
24
32
I
6.5
70
70
70
70
70
70
70
p
er
m
it
ted
t
o
tal
p
ip
e le
n
g
th
[
m
]
6.9
70
70
70
70
70
70
70
70
≥
9
100
100
100
100
100
100
100
100
100
100
90
90
U
6.5
120
120
120
120
120
120
120
120
120
120
120
120
6.9
120
120
120
120
120
120
120
120
120
120
120
120
120
120
≥
9
140
140
140
140
140
140
140
140
140
140
140
140
140
140
140
140
140
140
M
6.5
160
160
160
160
160
160
160
160
160
160
160
160
6.9
160
160
160
160
160
160
160
160
160
160
160
160
160
160
160
≥
9
180
180
180
180
180
180
180
180
180
180
180
180
180
180
180
180
180
180
180
Double U
6.5
155
155
155
155
155
155
155
155
155
155
155
155
155
155
155
155
6.9
165
165
165
165
165
165
165
165
165
165
165
165
165
165
165
165
165
165
≥
9
185
185
185
185
185
185
185
185
185
185
185
185
185
185
185
185
185
185
185
185
185