![Ampac TITANUS PRO SENS Скачать руководство пользователя страница 89](http://html.mh-extra.com/html/ampac/titanus-pro-sens/titanus-pro-sens_technical-manual_2934130089.webp)
Page 85
TITANUS
PRO·SENS
®
TECHNICAL MANUAL
Fig. 5.6: Installation of the reset board in
TITANUS
PRO·SENS
®
Installation TITANUS
®
In order to install the reset board in TITANUS
PRO · SENS
®
the following steps
are to be followed:
1
Carefully unlock the snap-in closures of the housing using a
screwdriver by simultaneously pressing in both clips located at
one side of the housing lid. Then, lift the lid carefully.
2
Pull the display board cable off the base board. Now remove the
housing lid.
3
Place the calculated end-of-line resistor31 R
ER
into the connection
terminal X1.
4
Fix the reset board to the mounting plate with 2 plastic spacers and
one plastic spacer.
5
Install the mounting plate equipped with the reset board in the
position shown in Fig. 5.5
in the
TITANUS
PRO·SENS
®
housing.
6
The electrical connection (X2) is described in section 5.6.4.
7
Re-connect the cable to the display board of the base board and
replace the housing lid.
8
Tighten the lid using the snap-in closures.
Due to its height, the reset board can only be installed in the position shown
in fig. 5.6.
31
end-of-line resistor not included, power 1/4W
INSTRUCTION