Page 53
TITANUS
PRO·SENS
®
TECHNICAL MANUAL
4.3
Special project planning
4.3.1
Project planning for individual aperture monitoring
The following system parameters apply to the detection of an individual or a
particular number of blocked aspiration apertures, depending on pipe
configuration.
The specifications according to Chapter 4.2 apply to project planning. The
following limit values and aperture diameters should also be taken into account.
Additional accessories (air filters, condensation separators, etc.) can influence
the maximum pipe length.
4.3.1.1
I-pipe system
1 pipe system
TITANUS
PRO · SENS
®
2 pipe systems
TITANUS
PRO · SENS
®
2
Fig. 4.29: I-shape pipe system for area protection
Limit values
Min. distance from TITANUS
to 1
st
sampling aperture
4 m
Max. distance from TITANUS
to 1st sampling aperture
20 m
Max. Distance from 1
st
sampling aperture to last
sampling aperture with low fan voltage 6.5 V – 6.9 V
with high fan voltage 9 V – 12 V
40 m
60 m
Max. Overall pipe length per pipe system
with low fan voltage 6.5 V – 6.9 V
with high fan voltage 9 V – 12 V
60 m
80 m
Min. distance between 2 aspiration apertures (d)
4 m
Max. distance between 2 aspiration apertures (d)
12 m
Max. number of aspiration apertures (n) per pipe system
10 pcs.