Page 63
TITANUS
PRO·SENS
®
TECHNICAL MANUAL
4.3.2.3 M-pipe system
1 pipe system
TITANUS
PRO ·SENS
®
2 pipe systems
TITANUS
PRO ·SENS
®
Fig. 4.15: M-pipe system for area protection
Limit values
Min. distance from TITANUS
to last T-piece
2 m
Max. distance from TITANUS
to T-piece
20 m
Max. branch length
20 m
Max. overall pipe length per pipe system
80 m
Max. number of aspiration apertures (n) per pipe
system
18 pcs.
Min. distance between 2 aspiration apertures (d)
0.1 m
Max. distance between 2 aspiration apertures (d)
4 m
Aspiration apertures
Number of
apertures
3
6
9
12
15
18
∅
of all aspiration
apertures in mm
29
)
5.0
3.6
3.0
3.0
2.5
2.5
29
Press cut diameter in aspiration-reducing film sheet